what is the formula to calculate the fault level current for
any substation?
Answer Posted / bala.a
Hai
we are using two method for find fault level.
1 - based on the supply voltage level
2. Based on the T/F capacity , Impedance, cable and
distance .
The first methios iS very simple but you will follow as
per TNEB standard. TNEB standard
11 KV - 350 mva
22 KV - 500 mva
33 KV -750 MVA
SO based on the aove standard
for 11 KV = 350 / RT 3 * 11 =18.39 KA
i.e = 11= Applied voltage or system voltage
| Is This Answer Correct ? | 18 Yes | 7 No |
Post New Answer View All Answers
Efficient electrical earthing in hard rock area
What is different bewteen low or high impedance busbar protection scheme
what is difference between line differential and transformer differential?
what is the breaking capacity and making capacity of circuit breaker and how
lenz law application and define
How we can come to know the substation range,without go through any name plate ?
Why using synchronising methed in DG's sets?
A d.c. Shunt motor is found suitable to drive fans because they require?
what happen when increase or decrease size of lamp,light.glass.
Hi, My plant daily consumption is calculated as 3.8MWH but my supplier has sanctioned an power of 2.6MW per day. how can i equal or distinguish this two factors
What is mean by STUB protection?
How many types of electric motors are there?
what is mean by parallel operation of permanent magnet generators
When we have earthing mesh or underground earthing network in industrial plants, weather we have NT-S or NT-C-S kind of earthing system, so eventually weather we must use 4 or 5 wire in 400 volt level (For example 3×150+70 mm2 or 5×150 mm2) in this connection I would like to know exactly the paragraph of IEC or IEEE number
Which type of air compressor is used now a days in the market. Keeping in mind of energy efficiency and maintenance points. Relevant documents may also be sent on mentioned email ids.