Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How to calculate cable sizes in sq.mm. with using motor KW?
Any formula there?

Answer Posted / abdool

3pahse power is P(in KiloWatt)=I.V.PF.(root 3).....
I=1.74 x P(KW)
EXAMPLE:
so, assume 3ph 400V 15KW motor, In=1.74x15=26.1 A,
& 15KW=20HP.....so 2xIn=Breaker rating= 52.2A
...choose 63A MCB

Cable size normally 20-25% higher than breaker to avoid
cable heat/burn accident in overcurrent fault. so, 1.25xIn=
62.64A so choose 80A Cable rating of 25mm2.

Is This Answer Correct ?    101 Yes 66 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

At full load wat is the motor p.f And at no load will is the motor p.f?

2056


Mention how NPN and PNP transistor works?

1226


You are of electrical field and you are going for software? Why

2264


What is the function of the circuit breaker failure relay?

2328


what is breathing?

1760


How seriving & testing of the HT & LT breakers are done. What are the standard Ir values on which we can come to know the test is passed or failed?

1988


Safety of dry type transformer

1908


in a solar power plant,we are going to step up the voltage 350V to 33kv, and to 132kv GSS. i want to ask that if it is possible that 315v/33kv is not possible because we also use 315v/11kv. or it should be 415v/33kv? is it effects generation or losses?  the second question is-generation is depends on LV winding? or LV winding design for generation voltage?

1674


what r PID controllers?why they r used?what is there purpose?plz Explain in detail

2029


working function importance of mdc meter

2115


what is the difference between Power and Distribution transformers ?

2092


What is the tests required for a 132 kV, 400 kV , 765 kV for a Circuit Breaker and Power Transformer before commissioning ?

1514


for 100 HP Induction motor service factor is 1.2(SF) we placed a VFD at the motor side load is balance with 0.3 Amp's Phase to Phase but at incoming of VFD load is un-balance with 10 to 20 Amp's what will be cause of load un balance

1898


explain the Trip supervision circuit

2094


what is difference between line differential and transformer differential?

1687