When measuring the Insulation resistance of a motor winding
(winding to earth) using a megger meter, Applied
voltage(1000V) was automatically reduced to 500V. and the
measured insulation resistance values are also very low (in
Kohm range) Can anyone give me a reason???
Answer Posted / sridhar
there are two reasons of getting the value low.
1. due to moisture in the motor
2. winding has become weak
to overcome these problems the methods can be adopted
1. heater or halogen lamp to be provided near to the
winding of the motor to bring the resistance value as per
std.
2. by this above method, the insulation resistance is not
upto the mark, the same winding can be overhauled to
achieve the required insulation resistance value.
Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
What is the meaning of 40X8X2 busbar dimensions for carring load of 400 Amps
what is sevice settings for mccb?How can be it setted?
why we use circuit breakers for switching instead of normal switching device?
Difference between rating factor of cable and derating factor of cable?
Explain RLC circuit?
Why the efficiency of generator is more than motor in swinburne's test
What is time invariant system?
why do we not use equivalent voltage source in negative sequence equivalent ckt.
What is the power factor of an alternator at no load?
what is the max. acceptable leakage current in 33kv bus bar
sir i had plane to do some project with the base of hopkinson test in AC supply its possible
How Calculet The UPS AH In Load
how to calculate the size of the HT cable
What is difference between safe PLC and normal PLC
list the type of vfd? wich is sutable for heating kiln?