What is loop checking ?
Answer Posted / nachiket dani
Usually used term in Distributed Control System design-
after the logic for the process has been programmed into
the DCS software,the controller cabinet alongwith the IO
modules is interfaced to the server on which the logic
resides.The IOs are assigned as required and circuit
continuity check is carried out-LOOP CHECKING..Outputs are
forced to some value(universal) or forced high(binary) and
the signal level is checked at the output Terminal block of
the IO module.Similarly for Input checks, Voltage/Current
is fed via a calibrator at the Input Terminal Block (1 by
1) and signal is detected via the monitoring mode on the
DCS software..This is to ensure circuit continuity and
scaling(signal limits)-it requires time and usually done as
pre-FAT or FAT procedure.
Is This Answer Correct ? | 42 Yes | 15 No |
Post New Answer View All Answers
Using your own examples solve a problem involving normal table. (experimental method and analysis)
I need control valve ISA hand book. Is there any site to download that big book containing all the pages. Written by Paul Friedmann
Calibration procedure for Electro magnetic Flow meter
Coal mill Instruments Equipments for cement plant And process diagram ?
Instrumentation Safe Guarding test. How to determine the interval time of the test. eg:Halfyearly,Every year,Every three years etc.
What is shielding effect?
Can I route 110 VDC and 24 VDC in a same Duct for our Interposing relay cabinet? IF yes or NO Please provide me IEEE Std. for the same. Please i required it on Urgent basis, i need to design IRP Cabinets and we have MCC 110VDC and Our Coil side is 24VDC, Please help as soon as possible.
What is the function of solenoid valve in on/off & shutdown valve and why it is not used in control valve normally?
Explain the mechanism behind the turbine meter.
How a conductivity sensor & analyzer work at boiler, whats the principle & science is beyond this,How conductivity sensor sence & convert signal & move toward analyzer & analyzer show reading in percent? also what is temperature compensate option in conductivity analyzer
How to Calibrate Flow Switch in field
how to commission furnace ( water heater)
why we take %i0.0 as input for twido plc
send me model hpcl questions pleas..........my mail id mohideen.dharvesh@gmail.com
how to calibrate Necleuonic level transmitter.?