Why, the starting current of 3 phase Induction Motor is 7
to 8 times its rated current?
Answer Posted / roysayan01
From the equivalent circuit of an induction motor it can be
seen that the the expression of current is
I=E/[(jX1+R1)+(jX2+R2/s)
Generally during running condition slip,s=0.03
i.e the value of slip is very low which increases the
resistance (R2/s) in the above eqn and as a result of which
current decreases
but
at starting s=1 and so the resistance (R2/s) is small and
the current is 7 to 8 times higher than the current during
running condition.
Hope i explained it vividly.
For ny doubt or query feel free to mail me at
roysayan01@gmail.com
| Is This Answer Correct ? | 46 Yes | 2 No |
Post New Answer View All Answers
Can any answer me ,What will be the range of C.T coil for L&T energy meter EM301 used for 180 kva DG set
ANY ONE TELL ME ABOUT generator synchronization panel panel to synchronise 3 gen of 250kva both automatic and manual. 2 gen output vol 415 3ph, 1 gen output vol 400 3ph SEND THE DETAILS DIAGRAM ON THIS EMAIL ADDRESS ayazleo@hotmail.com as soon as possilble best ragrds electrical engineer ayaz mahmood SAUDI TECH
Advantage of LT panel vs HT panel
If only R Phase is connected in 2 pole elcb, n is not connected than it will work or not in ground fault.
Compare jfet’s and mosfet’s.
1.main parts of generator? what is used A-check,B-check,C- check? 2.what is FM200 system in data centers? 3.difference between pac,ahu?
describe the Operation of induction generators from bus bars
what are the reasons of CT circuit faulty in busbar protection scheme?
I have iti elec, 1st aid, and 5 yrs experience in 7.5 mw power plant. Am i eligeble for 11kv license in telangana state..when, how to apply for that.?
What is the actual calculation for transformer short circuit test?.
What is load boxes ?
Any one can explaination about calibration with rotating sub standards?
According to underground cables a) stress b/w sheath & conductor is high b) inrush of core & conductor
if negative of DC supply used and positive is grounded through EGB, and if ELCB used in the system then is it sense the positive volatge and get tripped is it possible?
What is open delta Xformer? It's adavntages & Use?