Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the significance of KV & MVA rating of the
transformer and how they are related.

Answer Posted / eduardo

kV means kilo Volts, and is 1000 V. So 10kV means 10 000V.
This is the operating voltage. You must have another voltage
in the transformer. One is for the primary, and the other
for the secondary.

MVA means Mega Volt Ampere and is the power of the transformer.
1 MVA = 1 000 000 VA.

For example. If you have a transformer 10kV/400V and with 1
MVA, this means that at full charge is able to delivery in
the secodanry 1 000 000 VA / 400 V = 2 500 A.
He must be connect at a power line 10 kV and will delivery
400 V (till the load of the seconary reach 2 500A, after
that the value of the tension in the secondary begins to
drop, but this is another story).
In the primary the current will be 1 000 000 VA / 10 000 V =
100 A (at full charge).

Is This Answer Correct ?    25 Yes 24 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why lightning arrestor are made in two stack of insulator but why not cvt

2122


WHAT IS ELECTRICAL MAINTAINTENCE ?

2144


what is reverse power relay brief explanation and in b/w where it is connected

2087


I have 4 DG set with 1500KVA rating. system breakers are 11KV & alternator are 415 Volts. Between alternator & breaker one stepup transformer used. i want to Know what is max. resistance for body earthing & 415 & 11KV V Neuteal earthing. my fault current is 14 times for 2 sec.

2325


what is the safety of voltage power transformer(2250KVA0

2038


We have 750KVA DG set, we want to introduce REF relay with 1250/1A,CL PS,Current transformers.The lead distance of 2.5mm copper flexible cable from CT to relay is around 5mtrs.We would like to know the knee point votage(VK) & IM calculion for CT's

1973


Sir,In our company there are 3 caterpillar make(capacity:(1) 3.3KV,2.5MW(2)3.3KV,2.5MW & (3)3.3KV,1.9MW) & 1 deutz make (capacity:11KV,3.8MW)gas engines utilised,all are running in paralell. There are three transformer utilised,(1) 6.25MVA,3.3KV/22KV,Impedence voltage:6.7% used for two generator,both are 2.5MW(2)5.5MVA,3.3KV/22KV,Impedence voltage:7.2% used for one generator of 2.5MW & (3) 5.5MVA,11KV/22KV,Impedence voltage:7.8% used for one generator of 2.5MW.all generator breakers capacity of 1250Amps. Sir,I want the details of fault level calculation of generator,transformer individually & for whole system. If you require any information from me.feel free for contact me sir.pl.send the answer of my question as the earliest as possible.

2176


how can motor both beasrings insulation resistance can be check?

2074


what are the disadvantages in GIS over AIS

2491


can anyone explain 11kV 3core cable megger,hi pot test procedure with connection details?

3331


66kv under ground cable how to layaing in ground any special case two ckt r runing

2043


What is meant by vector group

2623


if 2 coil of 1000W connect in series and 200 v is applied across it . then what is the total power of coil when coil have only resistive load .

2012


what is EIB lighting control system? what is the advantages of this system?

3995


What is Negative Potential Bias

2352