what is STUB protection in tranmission system and switch
yard area?
Answer Posted / kamal ghasemi
When the line isolator is open and the voltage from cvt to
distance relay is absent and the bus isolator and breaker
are closed; if a fault occurs between the line isolator and
the ct a feature in dist. relay called stub protection
which is an instatanious none diretional oc relay sends
trip command to breaker.This is usually in test and service
conditions.
| Is This Answer Correct ? | 174 Yes | 14 No |
Post New Answer View All Answers
what will happen if there is a voltage leakage or current leakage in an electrical train
What are the types of power in electrical power?
Dear Mr B C pal...Can you plz. put some light on principle of operation of Z-Ct in conjunction to its use with 1Cx1000Sqmm HT Cables & Directional Ground Fault / Over Voltage Relays...Regd..Parag v K 9899115632
how to remover corona effect and hysteresis losses from contactor
Explain in brief description about the operation of DG sets.
for a 500 KVA connected load, I calculated 30% of capactor for power correction. Even after using 225 KVR capactor PF is not improving. What could be reason for low Phase correction factor?
how do u gauge the size of the cable ?for eg. consider a 300 sqmm L.T Cable.How do u determine the size of the cable seeing it pratically?
why the neutral line is not giving shock to us if we touch it ?
can you send me the placement papers of electrical engg. from companis like NTPC,DRDO,IOCL,HPCL,BPCL etc.?If,plz send as soon as possible.Thanks.
diff.between servo motor and ac motor
use of PIR in ehv breaker
how to calculate magnetic force genrated by a coil ?
What is difference and reason b/w -48V BTS system and 24 V BTS system. Plzzzzzzzzz tel me.
how to calulate short circuit current for the following: 1.cable connecting 11KV of 22KV/11KV transformer to 11Kv of 11KV/415V transformer 2.what cable size should i use.
3phase cable calculation formula by motor load