How to select a D.G set for calculated load of 110kW..?
Answer Posted / bal
Calculated load is 110kw.
considering 10% spare for future load growth
= 110 x 1.10
= 121kw
Operating at 0.8 pf,
= 121/0.8
= 151.25kVA
You can select the next available rating in market.
| Is This Answer Correct ? | 4 Yes | 11 No |
Post New Answer View All Answers
How isolater function when installed inelectrical 440V wiring
Why are short circuit ratings always 16kA,25kA,36kA and 50kA.Who has fixed these?
how cables go in and come out for distribution from the feeder pillar box?
1. If 8.35%Z means the percentage impedance of 132kV-line from power company, we will like to confirm its base capacity?
Can clean earth cable be considered as low current cable
how ct burden,magnetising current,ratio and knee point voltage are related & derived
A 50Hz,4-pole,3-phase,star-connected synchronous motor has a synchronous reactance of 12ohmsper phase and negligible armature resistances.the excitation is such as to give an open-circuit voltage of 13.2kilovolt.the motor is connected to 115kilovolt, 50hertz supplying. what maximum load can be the motor torque,line current and power factor?
why surge protectetor work explain with the help of circut diagram?
Explain how you intend to work under pressure to meet up with deadline target?
What do you mean by an instrument transformer?
What is the gross weight to copper ratio in slip ring induction motor of 4000 HP,6.6 kv, 372amp, 992 rpm GE motor.
Mention the difference between Analogue and Digital circuit?
EXPLAIN USE OF ROCKING ARRANGEMENT IN ELECTRIC HEATING?
ROC converges if pole and zero lies inside a) origin b) z=1 c) pole d) zero ? Explanation please? if ROC does not converges then?
A logic circuit that provides a HIGH output if one input or the other input, but not both, is HIGH, is a(n)?