how to calculate knee point voltage of current transformer?
Answer Posted / arvind negi
CT Knee Point Voltage Calculation Sheet
Primary Secondary Volt
Resistance Resistance Length
In MVA In AMP In kV In ohm In
ohm/km in Meter In %
1 CT ratio of the trasformer REF Protection -
1200 1 - - - - -
2 Transformer Rating, MVA 20 - - -
- - - -
3 % Impedance, %Z - - - -
- - - 13.9
4 Voltage of Line Side, KVLV - - -
11 - - - -
5 CT Secondary Resistance, RCT (ohm) - -
- - 6 - - -
6 Resistance of control cable of 2.5 Sq. mm.
- 8.5 -
7 Loop Length of Control Cable - - -
- - - 120
Calculation:
1) Fault Current at Primary Side of CT (kA) =
MVA/*100(%Z*1.732*KLV) 7.55
2) Fault Current at Secondary Side of CT, If (A)=
6.29
3) Cable Lead Resistance, RL (Ohm)=
1.02
4) Knee Point Voltage Vk (Volt) = 2If(RCT+2RL)
101.2
REMARKS : -
Knee Point Voltage of CT provided by CGL for REF CT
= 115V and for Differental CT = 200V are in order.
Is This Answer Correct ? | 8 Yes | 4 No |
Post New Answer View All Answers
what is basic difference betmeen normal & flame proof motor??
clarify types of motor operated valves and advantages
hi I have done 3 yrs diploma in electrical engg after 10+2. I have 16 years of work experience into design proposals sales and engg application development in LV/MV swithcgear and sub station automation field. I want to apply for immigration to new zealand but I am not sure whether I qualify or not since I dont have a degree. Can anyone advice? Thanks Riz
At the starting of dc motor and syn.motor and induction motor high current flowing through the winding. Due to this the windings burnt out. To avoid this different types of starters are used. But incase of transformer what Will be used (At starting no emf is induced in the primary winding)?
IN induction motor pf is increased using capacitors.what will be the effect on motor and system when very large capacitor is accidently installed and pf goes leading.
hi , i have 150 kw loud and we need 50 m cabil,i want to know wich size cabil we use. thanks
what is Anti-pumping?
Readings of ER300P Trivector meter
whats the application of voltage regulation? and whats the voltage regulation's device?
how is the testing of an REF relay? what are the test REF circuit having?
what is meant by neutral compensation factor and where it is used
our factory is going under construction mean time transformer 1000 kva 2 nos &load break swithch 12 kv & 4 nos 750 kva 2 nos & 380 kva 2 nos generator to be errcted.how to arrange earth pits &how to earth connect & neutral pit how to calculate in earth bit size.
what is destructive and non-destructive testing of welding
why using transformer and thyristor switch in 3 phase apfc panel
WITCH CARDS IN USE IN FIRE CONTROL PANEL.