what is the size(sq.mm) of these conductors
dog,rabbit,tiger,panther,mush,
Answer Posted / asmita
ACSR conductor Details
1=Sr No 2=Cross sectional area in sq.mm. (Copper equivalent)
3=Cross sectional area in sq.mm. (Aluminium
equivalent) 4=Current carrying capacity of conductor in
Amps. 5=Name of the conductor
1 2 3 4 5
1 13 21 75 Squirrel
2 16 26 80 Gopher
3 20 31 94 Weasel
4 25 42 136 Ferret
5 30 52 156 Rabbit
6 40 62 167 Mink
7 45 73 186 Beaver
8 48 78 204 Racoon
9 55 95 226 Cat
10 65 104 240 Dog
11 80 128 295 Tiger
12 95 154 335 Wolf
13 110 183 360 Lynx
14 130 207 400 Panther
15 140 233 430 Lion
16 160 258 470 Bear
17 185 317 525 Goat
18 225 336 550 Sheep
19 260 419 630 Deer
20 300 477 670 Elk
| Is This Answer Correct ? | 62 Yes | 27 No |
Post New Answer View All Answers
What is the difference between a verilog task and a verilog function?
we have 3.5MVA-11/6KV transformer. how can we calculate earth fault current and NGR calculation?
state the working of discharge lamp?
Installation resistance for whole installation of 16 kva & 25 KVA DTRA a) Between each conductor b) between conductor to earth c) installation resistance for each apparatus, each conductor to earth d) earth resistance for the system of earthing
I have doubt that the supply HZ (very low or high than rated ) may affect the power factor. is it true. ?
How to size Air Circuit breaker (ACB)? What is the most important factors?
why HT armoured cable does not glanding
What is meant by Load Encroachment in OHL Feeder Protection?
what is spadar bar .why I use in DC generator.
please send me the previous year's question papers of jindal GET exams
Trafo ratio is 11kV/6.6kv,Vector group is YND11. What will be the effect if secondary is used for earthed system.
application s to shunt coil
cc of scorpio?
Which Class insulation is prefered for the sandwich Busducts ? Why?
How to decide DO set rating of Transformer?