Answer Posted / raghavendran
NGr can be calculated by dividing the system voltage by the
allowable let through current from the resister to earrth.
say the system voltage is 600 volts and the allowable let
through current is 25A then the NGR value could be 600/25 =
24ohms.
Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
1.what is the reason for transformer and lightning arrester blast in 33kv system
Define gain margin?
Actually I have a doubt on neutral and earth.we use Ac power without taking neutral by connecting to earth,but at that time does it affects on efficiency of any electrical components or no? If yes how?
wHAT IS CAPACITANCE LATCHING? hOW TO CALCULATE CAPACITANCE LATCHING? hOW TO SOLVE THE PROBLEM IF CAPACITANCE LATCHING APPLIED?
what shall be no load voltage of 132/33 kV transformer ? is it 33 kv of 34.5 kV
why the electrolyte level in lead acid battery is maintained 2.5 cms above electrodes?
EXPLAIN THE ESSENTIAL FACTORS WHICH INFLUENCES THE CHOICE OF SITE FOR A HYDRO ELECTRIC POWER PLANT
HOW can i REuse the fused MLL LAMPS & GLS LAMPS at our factory
after how many spot we must chang secondry cable in portable spot welding gun?
which motor have relatively high power factor and what is reason for have high pf? 1.capacitor run motor 2.shaded pole motor 3.capacitor start motor 4.split phase motor
Mention the methods for starting an induction motor?
Why saturation region slowly shifted in the left side?
why do we carry out winding resistance test?
i am going to attaned the engineer (disign)iterview at HAL please give me duid line
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?