Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

1 Ton = ? amperes & power.

How much power 1.5 TON split AC consumes in an hour at 17
C , 26 C & 28 C (thermostat' temperature).

Answer Posted / ariel

COP = cooling capacity / compressor power; COP = 2.5 for
typical Direct Expansion AC units. Substitute the COP
value, 2.5 = Ton cooling/ kWcomp; or kWcomp = Ton
cooling / 2.5. Multiply Ton by 3.517 to convert it into kW
cooling. kWcomp = (3.517 / 2.5) x Ton; kWcomp = 1.4 x
Ton. This kWcomp is approximately equal to the system kW
based on AC units catalogs. MCA = (1.4/0.8 x Ton) / Voltage-
phase or MCA = 1.75 x Ton / Voltage-phase

Is This Answer Correct ?    27 Yes 40 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

define as synchronous generator

2144


how to flameproof electrical motor on the shaft?

2059


The principle of switching circuits for different types of batteries in application of storage systems

1962


Mention the difference between Analogue and Digital circuit?

1129


how to find ratio of CT & PT in 66/11kv 12 mva supply system ? explain with calculation.

2410


Tell me the reason of connecting domestic t/f primary in star or delta,and also secondary side.

1971


how to test the electrical panel.ht lt mcc pcc.

3780


in dc suppy frequency is zero why? if dc frequency is zero how to exist dc transients and ac transients

2127


Dear sir my name Ankit i m Diploma holder present working in Welspun Corp ltd Anjar as Asst.engg (salary 14400/month ctc) i Would like to change my company also i have selected in ford India pvt ltd Sanand as trainee Tech with salary 12000/month so please suggest me for changing my job hope for *ve response

2920


what questions will be asked for 11/33KV licence interview APSEB hyderabad. Can any one share question and answers.

18447


how u measure/calculate renge of capacitor,capacitor has no any rating tag.what is the theory of measure of capacitons.

1988


If there are two transformer having rating of 2.5mva, 6.6kv/440v(satr-star),and the load is 600kw then what is better to maintain less losses in transformer having both transformer in parellel or only single transformer connected to load? Please give calculated answer

2709


What will be the impact on motor performance if a LT motor is rewound with changed motor winding data as given below:- Original winding data: total 04 wires = 02 wires of 17 SWG + 02 wires of 16.5 SWG. Changed Winding data: total 03 wires of 15.5 SWG wire size Motor rating: 160KW, 740RPM, 415V, ID FAN application. Normal Running Current = 95% of FL Current.

2043


Dear all i am kumaravel. now in chennai. my work is control and relay panel auto cad designing.up to 11kv to 400kv then question is i am improving my knowledge. i want some books name and auther are available for this C&R panel related. plese any one help me

1776


What is Negative Potential Bias

2302