in split range control system we are using two control
valves,but we have only one positioner and one feed back
link.so how we use this one feed back link for two control
valves?
Answer Posted / vidnyan patil
one positioner using but it's output divided in two
position.one is 0-50 % and other is 50-100%.and second
think is one control valve 100% travel calibrated for 0-50
% positioner output,and second control valve 100% travel
calibrated for 50-100 % positioner output.so when
positioner output between 0-50% then one control valve will
operated and when positioner output between 50-100% then
second control valve will operated.
| Is This Answer Correct ? | 4 Yes | 6 No |
Post New Answer View All Answers
Using your own examples solve a problem involving normal table. (experimental method and analysis)
which processor is used in dcs.
any questions on motor and energy conversions machines?
how to calculate orifice sizing? and tell me if pipe size bet 50mm t0 200mm then we can use pipe flange??? and above 250mm pipe size should i use D & D/2 Flange? is it right or wrong?
Difference between dcs and plc including date processing and architecture.
1.what is the effect of vapour presuure in orifice plate flow measurement 2.which is more effective 2 pressure sensors or one single differential pressure sensor in orifice plate measurement 3.how to design a v/i converter and i/v converter 4.how many type of thermocouple are there 5.how many leads are there in thermocouple measurement 6.how pressure sensors are connected in level measurement in differential pressure method 7.what is the output of capacitive pressure sensor (ac or dc),how its o/p is signal charactarized 8.what is the physical meaning of discharge coeeficient,why it is calculated,orifice plate what is its value,why it is less than 1,Q at upstream is equal to or not equal to Q at downstream of orifice plate why?what is vena contracta in orifice plate 9.why rotameter is called variable area flowmeter,it can measure flow even if area is not varying,why it is made tapered 10.design a 10 bit counter ,which counter you will prefer 11.how to remove self heating error in RTD 12.which is more sensitive pt100 or pt50 13.why thermocouple are connected in parallel 14.what is lead contact error in RTD,how to avoid 15.what is P,PI,PID,PD controller,why there is no ID controller 16.what is override,split range,sequential,ratio,feedforward,cascade controller 17.why we moved from SR to JK and then JK to master slave JK flipflop,give correct reason 18.how to measure level of a closed container which contains vapour and liquid,remember no vapour gas should be leaked,so ultrasonic and capacitive is not an option,design another method 19.how to design horse race counter including sensors and signal conditioning element 20.what is bevelling
what is gas metering system? gas chromatograph? and gas compressors?
it is possible to check the fail safe condition in pressure transmitter. if possible how?
describe flow nozzel principle?
How to control flow variations in magnetic flow maters..... When i will provide proper earthing?
In bently nevada vibration monitoring system,what is the reason to maintain the Resistance of the probe + extension cable equal to 95 ohm? If possible explain the basic principle of measurement with detail electronic circuits.
How can you add value to this Industry if offered the job?
Explain the key components of control loop?
Explain why use mmwc unit?
why micro controller 8051/52's clock frequency is internally divide by 12 ?? and why it is further divide by 32 in UART serial communication ??