I have a 25kVA three phase transformer on our property.
Will this transformer be large enough to run a large home
with swimming pool, spa, 2 off full size reverse cycle air
conditioners to service a 100 square house (10,000 square
feet or 930 square metres)and the general power consumption
of this house without upgrading to a 63kVA transformer.
Answer Posted / s c budhiraja
Yes, this transformer is large enough for the house in
question.A normal house requires 100w/sq.meter area
including Air conditioning.The 930 Sq.meters reqire:9300w.
and add 10kw power reqired for the SPA. So total power
reqired is 19.3KW.A 25kva Transformer can supply power of
20kw at naormal power factor of 0.8. So the transformer is
is large enogh to meet the power requirement of the house
in consideration.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
what is the transformer rush current?
I meggared my 2c*70 sq mm AL AR XLPE cable. its one end show 50 M ohm . is my cable is safe for laying. I have only one phase and neutral.
Would you recommend to replace all oil filled cables with xlpe cable for hv transmission with the current technolgy for xlpe cable?
How do you determine the size of transformer radiators in a transformer?
In aerodynamic turbines which element is NOT there a.stator b.compressor c. Fuel intake system d.fans
What test must you do before powering up a circuit that you have been working on?
How to calculate phase to phase difference ?
What is inrush current? how can calculateit? what is the affect of it?
why did youi choose this career?
when qty of cable being purchased is not sufficient according to the standard,what should the inspector do to ensure its quality according to the standard?
Why are short circuit ratings always 16kA,25kA,36kA and 50kA.Who has fixed these?
What is Icu and Ics and what is difference b/w them. please tell me how to calculate a size of a copper bar for a system or a breaker... reply on... king.arish@gmail.com would be waiting for a logical answer.
what is the solution for meger test failed the MV cable?
The efficiency of a 100kva transformer is 0.98 at full load as well as half load , for this transformer what is the Copper loss at full load ?
two way ckt diagram can be drawn by how many ways? give diagram