I have a 25kVA three phase transformer on our property.
Will this transformer be large enough to run a large home
with swimming pool, spa, 2 off full size reverse cycle air
conditioners to service a 100 square house (10,000 square
feet or 930 square metres)and the general power consumption
of this house without upgrading to a 63kVA transformer.
Answer Posted / s c budhiraja
Yes, this transformer is large enough for the house in
question.A normal house requires 100w/sq.meter area
including Air conditioning.The 930 Sq.meters reqire:9300w.
and add 10kw power reqired for the SPA. So total power
reqired is 19.3KW.A 25kva Transformer can supply power of
20kw at naormal power factor of 0.8. So the transformer is
is large enogh to meet the power requirement of the house
in consideration.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What is lc oscillator?
What is different bewteen low or high impedance busbar protection scheme
how you taken aotitude test
5- What is the task (function) of the excitation and isolation transformers in power plant? 6- What is the task (function) of LCI (A), LCI (B) and LCI (COS) in power plant? : LCI (A) and LCI(B) are load commutating inverter for generator turbine starting. , LCI (COS) is load commutating inverter change over switch
why the value of k is more in shell typr transformers?
Please define ohm’s law for a.c (alternating current)?
critically criticize the application of ring main unit in power system
How to determine the breaking capacity such as break down current and break down voltage for VCB and CT's.
all the technical question with answers pleas send your email id ramar_eee@yahoo.com
IF ANYONE HAVE ANY QUESTION ASK ME AT MY MAIL anmol.bhardwaj5@gmail.com
what is buffer resistance starter.?.What is the working principle and where it is used..?
What will be the size of copper cable (each for 3 phase and 1 neutral) from Service connection Kit-Kat to Panel Board (i.e. to main switch) for a 6 pole 3-phase AC induction motor of 200 H.P. capacity? Amp-255 A, Frequency:- 1450 rpm.
how to avoid Saturation in C.T?
how can i find cable size from current rating?
which connection is safer series or parallel?usually which connection we prefer at home?