Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How many types of Control Modes in process control, plz
tell me all.....?

Answer Posted / sam

There is only two modes of control if you really think about it.
On/Off Control and PID Control.

Where some confusion can come in, is when you look at he
various CONTROLLER modes available on a DCS.
PID controllers are also sometimes linked together like in
cascade or feed forward control configuration, but the
control modes is still PID control.

Look at On/Off control:
You can have a open/close control valve in the field that is
controlled by the ESD or DCS system that will either open or
close this valve.
The ESD system do not do any control but it can open or
close a valve during a emergency as a step in it's blow down
or shut down sequence. This is in general not consider as
control just a action.
You can also have another open/close control valve in the
field that is controlling the level in a tank. In this case
it is connected to a Decap controller in the DCS. a Dcap
controller have a set-point that can be set to control the
level of the tank, but if a on/off valve is used as is, this
valve will open and close all the time to try and keep the
level on the set-point. So to prevent this the controller
have a small dead band around the set-point that can be
adjusted. This will then prevent the valve from opening and
closing until it reaches the dead-band threshold position.
Normally about 5% over and under the set-point. It is still
on/off control.

Looking at PID control:
Any mode in conjunction with proportional control is
possible on a PID controller it just depends on the
application. For example PID, PI, PD, P.
You can see them each as individual control modes if you
want, but I prefer to just stick to PID or on/off control
modes since there is a definite and distinct control mode
difference between the two. I see Dcap, PI, PD and P modes
as sub divisions on the two main control modes.
P = Proportional
I = Integral
D = Derivative
Good Luck

Is This Answer Correct ?    5 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

dear sir we have insatlled positioner model no.sipart PS2 make Siemens at our control valves . now problem is if we want to increase the response of valve opening speedy /fast. what parameters do we change for positioner ? any idea. please guide us.

1897


what are the different types of Protocols? & their applications.

30691


How is automatic reference junction compensation carried out in temperature recorders?

1099


Can I route 110 VDC and 24 VDC in a same Duct for our Interposing relay cabinet? IF yes or NO Please provide me IEEE Std. for the same. Please i required it on Urgent basis, i need to design IRP Cabinets and we have MCC 110VDC and Our Coil side is 24VDC, Please help as soon as possible.

2280


Q1]IF THE RANGE FOR FLOW IS -35 TO 125 WHAT WILL BE THE SPAN FOR ABSOLUTE AND FOR NORMAL? Q2]HOW TO CALIBRATE CAPILLARY TYPE LT? Q3]HOW MANY ERROR CALCULATIONS ARE THERE USED IN PROCESS INDUSTRIES? Q4]HOW TO CALIBRATE TEMPERATURE TRANSMITTER? Q5] HOW TO CALIBRATE LEVEL TROLL AND HOW TO CONNECT? Q6]PLEASE TELL ME THE BASIC FOR INSTRUMENTATION WHICH IS APPLIED FOR CALIBRATION AND FOR ALL? PLEASE MAIL THE ANSWER TO honest_yes@yahoo.in

1942


why we use the ac supply load cell>?can we use the dc supply load cell?advantages and disadvantage of the ac supply load cell?

6414


pls give me presant awerness quistion and answer in my emailid.

2869


What is Span Error

697


HOW TO CHOOSE FREAQUENCY IN FMCW TYPE RADAR INSTRUMENTS. DESIGN BASIS OR DESIGN CALCULATONS ?

2183


CONTROL VALVE OPERATING IN MANUAL BUT NOT IN MANUAL. WHAT SHOULD BE THE PROBLEM ?

1900


dear friends, i have seen flow as the selection critriea in presure guage (bourdon tube) and i would like to know what is the relation between flow and performance of pressure guage other parameters i found in the data sheet are pressure max. 1ksc temperature max. - 50 deg c line size - 80NB operating range - 1ksc pr. guage range - 0-2 ksc thank u,

2175


Where Can i take a SPI INtools training in Mumbai? In Rolta India Ltd to whom I should approach regarding of SPI INtools Training?

2786


what is 24vdc live and dry supply

2273


What are the error values can accepted in flow transmitter calibration?could u give any formula for this?

1914


what is output of FOUNDATION FIELD BUS transmitter

2151