how choose conductor &caple&wire depending upon the load
Answer Posted / ccic
Cable/wire , i.e. the conductor should be rated for at
least 125% of the FLA. The upstream CB protecting this
conductor should also be rated similarly, i.e. for a load
with 100A as FLA, the cable should be able to carry at
least 125 A. The cable derating factors (type of cable,
type of installation, ambient condicions, Voltage Drop etc)
should then be used to select the ACTUAL cable. The CB
should be rated for 125 A (Instantaneous Trip setting)
| Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
how electical engineer is related to apsrtc (general) post? if they ask a question in interview as why did u choose this job what shd be answer
what the Microsoft .NET framework is?
what is the difference between transformer,converter and transducer
What are the advantages and disadvantages of the ac motors?
i have a 4 Mva transformer 34.5 kv / 480-277 v and i used 2 parallel 3200 amp bus duct for the secondary feeder using 3 ply of bus bar ( 3/8" x 5" ) as a common where the flexible link terminated and 6300 amps breaker for the main, the lower bus duct reaches 70 degrees and the upper bus duct reaches 55 degrees when i used thermal scanner. why the temperature is not balance when the load reaches 3600 amps.
How to calculate the electrical load for a standard telecom BTS shelter and choose the DG set capacity for the same load?
How PSV sizing being done
What are the transformer losses?
WHAT IS THE MEANING OG (li = 7 In)
if a.c supply is given to the motor,, what happen?
If Neutral Grounding Resistor (GR) failed/shorted. Is it repairable.
How they LT panel busbar size choose
what is proper capacitor placement? How to evaluate capacitor size?
our industries ht line so power fluctation(once drop of power please rectify causes
What is the formula to calculate the rating of power cable for three phase current.