what is the meaning if the control valve CV is 27,in terms
of selecting procedure?
Answer Posted / sam
Flow coefficient is the proportional constant between
pressure drop and flow rate and it is determined
experimentally by valve manufactures. It is expressed as the
flow rate of water in m3/h for a pressure drop of 1 bar
across a flow passage.
Flow coefficient = Cv or Kv
Cv = Imperial
Kv = Metric
Selecting the correct size control valve:
When the flow coefficient is calculated for the required
flow rate and known pressure drop, the selection of a proper
control valve is normally done by selecting a control valve
with the next bigger flow coefficient(cv)
So in your case here are some info that might help,
With a control valve with a cv of 27 in a clean water line
with a 100mm pipe dia size, a DP across the valve of 1Bar
will give a volumetric flow rate of 23m3/h and a fluid
velocity of 2973m/h
With a control valve with a cv of 27 in a clean water line
with a 200mm pipe dia size, a DP across the valve of 1Bar
will give a volumetric flow rate of 23m3/h and a fluid
velocity of 743m/h
With a control valve with a cv of 27 in a clean water line
with a 300mm pipe dia size, a DP across the valve of 1Bar
will give a volumetric flow rate of 23m3/h and a fluid
velocity of 330m/h.
So the volumetric flow rate stays the same regardless of
pipe dia if the DP stays the same. The only thing that will
change is the flow velocity.
So,
With a control valve with a cv of 27 in a clean water line
with a 100mm pipe dia size, a DP across the valve of 1Bar
will give a volumetric flow rate of 23m3/h and a fluid
velocity of 2973m/h
With a control valve with a cv of 27 in a clean water line
with a 100mm pipe dia size, a DP across the valve of 2Bar
will give a volumetric flow rate of 33m3/h and a fluid
velocity of 4205m/h
With a control valve with a cv of 27 in a clean water line
with a 100mm pipe dia size, a DP across the valve of 3Bar
will give a volumetric flow rate of 40m3/h and a fluid
velocity of 5151m/h
And,
With a control valve with a cv of 27 in a clean water line
with a 200mm pipe dia size, a DP across the valve of 1Bar
will give a volumetric flow rate of 23m3/h and a fluid
velocity of 743m/h
With a control valve with a cv of 27 in a clean water line
with a 200mm pipe dia size, a DP across the valve of 2Bar
will give a volumetric flow rate of 33m3/h and a fluid
velocity of 1051m/h
With a control valve with a cv of 27 in a clean water line
with a 200mm pipe dia size, a DP across the valve of 3Bar
will give a volumetric flow rate of 40m3/h and a fluid
velocity of 1288m/h
And,
With a control valve with a cv of 27 in a clean water line
with a 300mm pipe dia size, a DP across the valve of 1Bar
will give a volumetric flow rate of 23m3/h and a fluid
velocity of 330m/h
With a control valve with a cv of 27 in a clean water line
with a 300mm pipe dia size, a DP across the valve of 2Bar
will give a volumetric flow rate of 33m3/h and a fluid
velocity of 467m/h
With a control valve with a cv of 27 in a clean water line
with a 300mm pipe dia size, a DP across the valve of 3Bar
will give a volumetric flow rate of 40m3/h and a fluid
velocity of 572m/h
So to summarize if you have a control valve with a cv of 27
you need to have a look at the maximum volumetric flow rate
that will be required in the line that this control valve
will be installed in, in order to see if this valve is big
enough to control this flow.
Keep in mind the perfect control position for any control
valve is between 40 to 60% valve opening. You need to select
a valve with a cv that will allow control to be in that area
under normal operating conditions, so it is important to
consider minimum, normal and maximum flow conditions during
the selection process. To be safe select the next bigger cv
than what your calculations says the correct size will be.
Good luck
Is This Answer Correct ? | 6 Yes | 3 No |
Post New Answer View All Answers
Programmable Logic control.
Q1]IF THE RANGE FOR FLOW IS -35 TO 125 WHAT WILL BE THE SPAN FOR ABSOLUTE AND FOR NORMAL? Q2]HOW TO CALIBRATE CAPILLARY TYPE LT? Q3]HOW MANY ERROR CALCULATIONS ARE THERE USED IN PROCESS INDUSTRIES? Q4]HOW TO CALIBRATE TEMPERATURE TRANSMITTER? Q5] HOW TO CALIBRATE LEVEL TROLL AND HOW TO CONNECT? Q6]PLEASE TELL ME THE BASIC FOR INSTRUMENTATION WHICH IS APPLIED FOR CALIBRATION AND FOR ALL? PLEASE MAIL THE ANSWER TO honest_yes@yahoo.in
What is the difference between uv and ir scanners? and what is the workig principle of both
selection criteria of control valve? and selection criteria of actuator explain in brief?
In turbine what does term CDP, NI, NH, HSSOC means.
what is installation and commissioning of (fat & sat) of power plant dcs ? this question keeps in desirable conditions of one company .
how can i check vortex shedder bar it is ok? if there is ohms condition are shown correct?
Calibration procedure for Electro magnetic Flow meter
any one can send me instrumentation previous interview papers? I prepare for MNC Company Interviews? my mail id- Rakesh.Golla@dodsaldxb.ae , and another mail rakesh.gvk@gmail.com
What is the use of GMV in turbine?
how to calibrate Necleuonic level transmitter.?
what do u mean by compensation n pid tunning?in pid tunning what you tunned?is it possible 2 tune p i d
How can measure flow in oil line?which type of transmitter is generally used?
WHAT IS THE CAM POSITION IN CONTROL VALVE POSITIONER ? WHY IT IS USED?
why we r opening HOT BYPASS valve during startup of a compressor?