Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to calibate level transmiter ?range -150 to +150.what
is the zero and span?

Answer Posted / sam

This means that your transmitter is capable of measuring a
differential pressure of 300. Whatever this units of measure
is. You can calibrate the transmitter for any of the
following conditions:
LRV = -150 = 0%
URV = +150 = 100%
Therefore span = 300 UOM (units of measure)
or
LRV = 0 = 0%
URV = +150 = 100%
Therefore span = 150 UOM (units of measure)
or
LRV = -150 = 0%
URV = 0 = 100%
Therefore span = 150 UOM (units of measure)
or
You can also calibrate the tx for any span in between this
300 range.
To find the correct Z/S values for your application measure
the distance from the transmitter to zero position on the
vessel and multiply this with the density of the product you
want to measure (LRV). Do the same with your 100% (URV) value.
Good luck

Is This Answer Correct ?    21 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the protection system in solar turbine compressor

2199


Draw a group of instruments interlocked to a Pump & Motor?

1294


why we use the ac supply load cell>?can we use the dc supply load cell?advantages and disadvantage of the ac supply load cell?

6412


What is the meaning of wet leg

1250


please tell me what is a light up procedure of Cfbc boiler and what it's axuillaries of cfbc boiler?

8669


How do you identify between actual alarm and false alarm in a Temperature Transmitter in SCADA based Control System

1372


while am calibrating Drager polytron 2IR flame gas detector occured non zero status.how can i get zero status?

2209


TEMPERATURE VARIATION FOR FREQUENTLY.

2048


How u will setup SPI(2007) on Citrix Server (Thin Client Mode)? Plz Justify?

2022


What is difference between Ionization heat and bimetallic heat

1670


what would be the minimum flow rate that we can measure on rotameter..?

2097


Explain bernoulli’s theorem. State its application.

1184


Which type of pressure can be measured by primary elements?

1049


How to Calibrate Vibration Probe (Axial, Redial) in field

1142


Can Any body tell me how to check Modbus Settings in ER300N L&T trivector meter?

2595