Answer Posted / anil bhatia
sorry my earliar reply there was a mistake ignore it .
new reply
Emf in primary
E1=4.44fN1Bm
Emf in secondary
E2=4.44fN2Bm
where Bm is maximum /peak flux density, in weber /sq m
(Tesla)
under no load condition E!=v1, E2=v2 , assuming negligible
Magnetizing current.
equation is v=4.44FNBm
or say V/N= 4.44FBm
1) Thus reduction in frequency F causes the increase in
flux and their by flux density.
2) Thus increase in volt/turn , V/N causes increase in the
flux and thereby flux density.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Dear sir, In our plant have Station Transformer having capacity,i want to know, why LV side 40 - 40MVA is given? & how we can get 6.3 KV supply from tertiary(i.e. Open delta connection), Vector Group YNyn0 - yn0 +d MVA Rating 80MVA / 40 - 40MVA + 26.7MVA Voltage rating 420 (Tap range +6,to -10)81.25% /11.5KV - 11.5KV +6.3KV
what is the meaning of 5% droop or 7% droop in AVR?
DIFFERENCE BETWEEN NORMAL TRAFO AND THRISTER TRAFO?
10 tube light connect in mcb breaker.one tube light is fault.so breaker is tribe.how fault is rectified.(using 3wire phase,earth,neutral)
How does the phase sequence controller works, how it identifies the phases? confirm working principle
What do you mean by screen of power cables?
Can we use 230VAC, 63A MCB for 120VAC, 63A supplied heaters load?
which stabilizer is better ? AVR, Servo Stabilizer, Static stabilizer etc & why explain it
Capacitor is load free component but why ampere meter shows current when capacitor bank breaker close?
2. What are the parameters of EHT sub-station?
Iin ESP why positive is grounded ? why not negative ?
What are steps to be taken while designing of DYN11 distribution transformer to achieve magnetising balance?
If you don’t have coal, salt and copper, then how would you earth your connection temporarily at a camp site.?
How to select a cable size for particular load?
What is the difference between PS & metering CT (5p20,0.5 etc.)? Why in PS class CT only Vk is given ? Is PS class CT is more accurate than metering CT?