What is the exact load current needed for a place which has
100nos of bulb of each 100w?

Answer Posted / errol

assuming a 230V power supply:
I=P/V where P= 100W x 100pcs = 10,000watts
Total current, I, therefore is 10,000W/230V = 43.48A. The power factor is 100% bearing in mind that bulbs are resistive loads.

Is This Answer Correct ?    7 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is a advantage of Self Reset Lockout ? On Fault breaker get trip & fault no longer exist then self reset lockout how inform us?

1370


How to calculate Number of Earthing Pits....???

1111


what kind of quetions will ask in BHEL in interview? Plz help me?

1572


LT cable fault chaecking equipment and to find out the distance at what distence it failure . Name and where it is available?

1668


what is allowable ac mixing in dc

1535






what is diff. between earthing grid,earthing mess, earting grid?

1860


In the magnetic fluxes, what is the role of armature reaction?

689


what is the safety points of vaccum circuit breaker.

1634


IN SINGLE PH TRANSFORMER IF LEKAGE IMPEDANCE DROP IS NEGLECTED ,THE FLUX IN THE MAGNETIC CORE and the lekage flux linking a winding are a)proportional to the applied v to the winding i respectively.

1627


why three phase capacitor takes unbalanced current in capacitor bank?

1003


how to calculate the conductor size for certain KV transmission line and distribution line?

2007


please give me solution to rectify the emi(electromagnetic interference)

1438


How can we calculate the efficiency of a Running (On-Load) Motor ? What parameters are required and what is the method ?

1525


Wind mill

1411


What is the criteria that generally follow by distribution licenses to fix contact demand of their industrial customers?

1101