What core magnetic balance test of transformer?
How to do this test in a three phase Star delta (star-LV,
Delta-HV) transformer?
How to measure and where to measure?
thanks and regards
Austin
Answer Posted / ketan
i am ketan more (be electrical)
magnetic balance test
1) step1 given 400v R&Y PHASE ONLY. THAT TIME B PHASE OPEN
OR NOT CONNECTED SUPPLY
MEASURE VOLTAGE RY & YB & BR
READING IS RY=400V (GIVEN VOLTAGE)
YB= (3/4 RY) VOLTAGE
BR= (1/4 RY) VOLTAGE
THISE READING COME MEANS TRANSFORMER IS OK OR MAGNETIC
BALANCE OF PHASE IS OK
| Is This Answer Correct ? | 6 Yes | 12 No |
Post New Answer View All Answers
how to calculate transformer turn primary & secondary side 11kv to 420v
what is the generator rating for 40 amp load of 3phase motor.?? 400v voltage of generator... plz tell me with formula its urgent...plzzz... and also tell me that this 40 amp at all phases mean 40 amp on red,40 amp on yellow,40 amp on blue...... or the total sum of that 3phase is 40 amp....
Which Class insulation is prefered for the sandwich Busducts ? Why?
What is Phase to Phase clearance for 800V System Operating Voltage as per IEC61439
i need the details about bhel exam.how to apply for that.please send to my email-id.thenmozhi2k7@gmail.com
Why do we need interlocking in a HT metering or Ring main unit switchgear?
There is any especial requirement for motor to drive through with VFD?
Work done in a free expansion process is
Electromagnetic torque developed by the motor is compared to shaft torque. A less B same C depends on motor design D more
What do you understand by external characteristics of a d.c. Generator?
Define branch?
how to build a network which step down 415v to 1v rms
how to calculate the step resistance for slipring induction motor,how you deside the no of step for that?
is it possible to turn on the single phase star delta on delay timer using 24 v dc ?
1600kva capacity Transformers how the bucholz relay,Oil temperature,winding,surge relay relays setting are to be done