If DG runing time neutral is disconnected what will be the
effect in Engine and Electricial panel.
Answer Posted / pillay
if the DG is not loaded nothing will happen and there wil be
no damage.While loaded if the load has got no single phase
load also nothing will happen and everything will continue
as normal.If you have connected a load of single phase
nature and if the load is balanced or near balanced then
also if the neutral is removed no damage will happen or you
may not see any changes because the neutral current is
balanced at the phases. but if you have connected an
unbalanced load or the load changes often than the voltages across the phases will be inconsistent.this is a very
damaging situation because the voltage can be as though you
have connected across a 2 phase supply the voltage across
the circuit is determined by the amount of current flow in
each circuit
| Is This Answer Correct ? | 2 Yes | 3 No |
Post New Answer View All Answers
what is plunger and what's the use of it in motor alignment?
If I want to connect a capacitor bank on the HT side of a 11kV/415V, 3 phase delta-star distribution transformer to supply Reactive power to it..what practical specifications of a Capacitor bank that can i've??please reply..
How to dimensioning SDCCH, LAPD and CS7 signaling on GSM?
Why AC current leads voltage in capacitor and how?
what are the difference between PLC and embedded
How to design the no. of ceiling fans required in 5mtr X 10 mtr X 3 Mtr hight room?
What is effect on in zone and out zone fault if CT chosen for phase side is Vk/2<5mA and Neutral side is Vk/2<15mA on REF protection of Transformer
what is the difference between an alternator and a synchronous motor
in ACB breaker requireding 3200Amps. buscoupler getting OFF mode and again it reset and getting normal position give me a required answer?
What is the method to solve circuit using source transformation?
How can calculate the earthing strip of Copper/GI for rating of 30kV,discharge current 10KA Lightning arrester.
What is the unit audit? if our Max demand is something and we found much more unit then how to improve our max demand?
During regenerative breaking= A rotating magnetic field is reversed B slip is positive C torque is positive D slip is negative
why we use the 100% and 95% stator earth fault protection for the synchronus generator ?
how single phase preventer works ?