If DG runing time neutral is disconnected what will be the
effect in Engine and Electricial panel.
Answer Posted / pillay
if the DG is not loaded nothing will happen and there wil be
no damage.While loaded if the load has got no single phase
load also nothing will happen and everything will continue
as normal.If you have connected a load of single phase
nature and if the load is balanced or near balanced then
also if the neutral is removed no damage will happen or you
may not see any changes because the neutral current is
balanced at the phases. but if you have connected an
unbalanced load or the load changes often than the voltages across the phases will be inconsistent.this is a very
damaging situation because the voltage can be as though you
have connected across a 2 phase supply the voltage across
the circuit is determined by the amount of current flow in
each circuit
| Is This Answer Correct ? | 2 Yes | 3 No |
Post New Answer View All Answers
how much GROUND & NEUTRAL VOLT maintain in data center.
I am inpecting a 10kVA UPS what tests should i do and should i observe?
How impulse levels are calculated that for 11kV impulse is 75kvp, for 24kV impulse is 125kvp ?
Is it possible to connect a safety device in to parallel?
Define damping ratio.
What is essential to prove safe isolation of electrical circuit?
What are hrc fuses and where it is used?
briefly explain the main blocks found in a microprocessor based system
How can we choose the rating of submersible motors
What are the specifications for getting approval of Substation?
can anyone tell me can the electromagnetic waves can be reflected back?if so how &by which material it can be reflected back?please tell me so that it can help to my wireless power trasnmission device.
What is the reason of polyphase induction motor tripping suddenly on high current during running at 70% laod? Motor IR , winding resistance & inductance balance. Motor no load current is balance and ok as per mgfr. data.
what do w do when the output of generator is fluctuating?
what will be the maximum winding temperature of 6.6kv HT motor 450kw, Full load current 49A. 50Hz Frequency.
how do you test tachos and servos