Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How to calculate unit consumption on the basis of load.
kWH=kwXhrs.is it correct? kw is motor load.What is unit
consumption at 100% load, 50% load & on no load.

Answer Posted / shannu

Unit consumption is KW x Hrs.

But while you need to calculate the KWH consumed by a motor,
multiplying KW of motor (nameplate KW) and hour will not
give you the energy consumed. This is because the name plate
KW in a motor is not the electrical power, but the
mechanical power output provided by the motor (Electrical
Power = Frictional losses + Eddy current losses + Copper
losses + air gap losses + Mechanical power). In order to
calculate the energy consumed by the motor you can use the
formula

single phase AC = Voltage x Rated current x Power factor x
Hrs run. (100% load)

3 Phase AC = 1.732 x Voltage x Rated Current x Power factor
x Hrs run. (100% load)

Normally the power factor of motor is considered between 0.8
to 0.85 at full load operation.

At no-load, motor will take approx 40% of its rated full
load current (again this depends on the design of motor, but
normally assumed to be near 40%). So at 50% load, the motor
will take a current around 70 to 75% of its full load rated
current. so we can approximate as

energy consumed at 50% load (motor - 3 phaase) = 1.732 x
Voltage x 75% rated full load current x power factor x Hrs run .

at no load = 1.732 x Voltage x 40% of rated current x power
factor x Hrs run.

Is This Answer Correct ?    32 Yes 7 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is a types of short circuit and what is a types of distance protection tests

2262


How to find out damper winding failure for synchronous machine?

1513


what are the interview question asked in wind mill about electrical

2376


What should be the values of settling time, peak time, steady state error, overshoot, rise time, MPOS (Maximum percent over shoot) to keep the system in transient state, to keep the system in steady state ?

2259


How many types oil using in transformer ? How many letars using in transformer..?

2110


why using transformer and thyristor switch in 3 phase apfc panel

2884


What happen to generator if i have unbalanced load?

2110


what is x'mer ,isolation x'mer & yltra-isolation x'mer?????

2486


which stabilizer is better ? AVR, Servo Stabilizer, Static stabilizer etc & why explain it

2877


What are the three types of compensators?

1105


A low wet bulb temperature indicates

1165


in star-delta tranformer,if the input of star connection is 400/7v 3 kva then what is the output of delta connection?

2134


What is stepper motor. What is its uses?

1274


What is the rating of circuit breaker needed for 300 KVA load in 33 KV supply line in a transformer of 33 KV / 415 Volt ?

1780


How to see the inductance in a transmission lines

2147