How to calculate unit consumption on the basis of load.
kWH=kwXhrs.is it correct? kw is motor load.What is unit
consumption at 100% load, 50% load & on no load.
Answer Posted / shannu
Unit consumption is KW x Hrs.
But while you need to calculate the KWH consumed by a motor,
multiplying KW of motor (nameplate KW) and hour will not
give you the energy consumed. This is because the name plate
KW in a motor is not the electrical power, but the
mechanical power output provided by the motor (Electrical
Power = Frictional losses + Eddy current losses + Copper
losses + air gap losses + Mechanical power). In order to
calculate the energy consumed by the motor you can use the
formula
single phase AC = Voltage x Rated current x Power factor x
Hrs run. (100% load)
3 Phase AC = 1.732 x Voltage x Rated Current x Power factor
x Hrs run. (100% load)
Normally the power factor of motor is considered between 0.8
to 0.85 at full load operation.
At no-load, motor will take approx 40% of its rated full
load current (again this depends on the design of motor, but
normally assumed to be near 40%). So at 50% load, the motor
will take a current around 70 to 75% of its full load rated
current. so we can approximate as
energy consumed at 50% load (motor - 3 phaase) = 1.732 x
Voltage x 75% rated full load current x power factor x Hrs run .
at no load = 1.732 x Voltage x 40% of rated current x power
factor x Hrs run.
| Is This Answer Correct ? | 32 Yes | 7 No |
Post New Answer View All Answers
Why Stabilising Resistor used in REF circuit ?
How to design the earth grid for lightning protection in an industry
How many types of electric motors are there?
In the ACB breaker capacity is 2000Amp but this each phase taken 1250 But total beldibg load is 600amp or 700amp watt is the problem
Define transfer function?
what is the synchronous timer ? and it applications.
Details about Flux Compensated magnetic Amplifer starter for motors
what is is the potential diffrence between two phase ?
why power not passes in plastic and rubber material
what are carbondioxide and dcp used in fire extinguishers
how to calculate earth fault relay current and CBCT ratio
Where is servomechanism used?
please explain how to do 'pole drop test' on generator?
how to interlock 3 incomer-ACB,1 buscoupler ACB,... pls answer this question and if possible send me the ckt diagram..haifriends2910@gmail.com
how much winding resistance of 0.75kw to 12.5kw 3ph sqwiralcage induction motor?