If we feed 230V ac supply to a full wave rectifare, what &
how much will be the out put voltage?
Answer Posted / gees
325 volts ( with no load applied ).This is because the
capacitor, normally on the output charges up to the PEAK
vale of the waveform ( 1.414 times the RMS value of 230V )
| Is This Answer Correct ? | 6 Yes | 0 No |
Post New Answer View All Answers
A 400KVA transformer has 400 Hz frequency. If the frequency is changed to 50 Hz, then what will be the new KVA rating?
Why to keep capacitor bank off while generator running.
i am in need of AC SYNCHRONUS MOTOR 30KW. ANY ONE KNOWS THE MANUFACTURER OF SAME. ALSO MOSFET AC CONVERTER 20KVA CONT.OUTPUT.
IN electrical field, WHAT ALL THINGS THE CUSTOMER WILL ASK WHILE ORDERING FOR LT PANEL (ALL TYPES OF LOW TENSION PANEL)
why we have and use 3 phase not 2 or 4 or other in power system?
3 shows a 415 V, 3-phase generator supplying a 3-phase 415/110 V transformer. Draw the individual and combined impedance diagrams to a base of 10 kVA. Determine the system fault kVA and the fault currents at the 415 V and 110 V busbars for short circuit faults on the transformer input or output terminals. Work in p.u. values of impedances.
How much weight an electrical engine can pull??
does the Trivector Meter of three phase automatically takes care of the low power factor and gives the reading accordigly or it does not take care of the Power factor while giving the readings please explain
What is the de rating factor of cable? What is the importance of the de rating factor in cable selection?
What is the use of lag compensator?
What are the factors which influence the choice of specific magnetic and electric loadings of a synchronous machine?
how ct burden,magnetising current,ratio and knee point voltage are related & derived
what is the differation bewreen kwh & fundamental kwh in electronic trivector meters
WHAT ARE THE CHARACTERISTICS OF AN VOLTAG AMPLIFIER
bus bar design conditions and sizing pls tell me quickly