Why generally the Rating of Transformers are in additions
of 11 i.e. 11 kVA, 22 kVa, 33 kVA, etc........
Answer Posted / p. h. godavary
Here the question is not correct. Transformer ratings are never in multiples of 11.
It is the Generator voltages that are in multiples of Form factor 1.1(approx.). The voltages are 3300V, 6600V, 11000V. Consequently the normal distribution / transmitting voltages used are 3.3KV, 6.6KV, 11KV, 33KV, 66KV 110KV, .......
Form factor of an alternating current waveform is the ratio of the RMS (Root Mean Square) value to the Average Value of the waveform]. In the case of a sinusoidal wave i.e. , an analogue wave, the form factor is approximately 1.11
| Is This Answer Correct ? | 34 Yes | 3 No |
Post New Answer View All Answers
Draw the line diagram of diffretial relay connected to transformer?
pls someone send me sample question papers along with the key.thanks in advance
How will change the frequency in distribution side?
Which device is used for the source of emission of electrons in a crt?
why co incidence factor considered in transformer sizing?
How much load can be taken for chiller from 1500 kva transformer
What is the method of estamating of cable, CB,MCB ?
How can calculate the rating of a servo stabilizer for given a specific load
what questions are asked in the interview for the post of an electrical maintenance engineer in FMCG companies?
how can i determine the KVA/MVA rating of transformer precisely?? is there any standard test?????
briefly explain principle of resistance welding
According to IEC60034-14, When the vibration monitoring system required for motor Bearing. above which KW, it is required? and for what type of bearing the vibration probe is provided.
What is the difference between AC and DC injection methods for rotor earth fault protection
What is the actual calculation for transformer short circuit test?.
Can we use 230VAC, 63A MCB for 120VAC, 63A supplied heaters load?