can we connect both delta and star to the transformer
secondary and for what reason?

Answer Posted / gopi

suppose in transformer one side of coil of each phase can
connect to ground potential. It means that the insulation
strength of transformer can be reduced compared with Delta
connection . It realize cost down of transformer. Delta
connected coil need same insulation strength on both side
of coil, so it need more cost for insulation. But in Star
connection, harmonics problem will appear. In case of Delta
connection, harmonics current is circulating in delta-
connected coils and not appear in distribution line. If the
harmonic current was there, it will be a cause of over heat
of lead-phase capacitor, lag-phase inductance and
transformaer.

Is This Answer Correct ?    1 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Do you know what is dry-out test in x'mer

2315


state basic meaning of 'INDUSTIAL AUTOMATION'?

1498


Efficient electrical earthing in hard rock area

1161


Why PT voltages are measured with respect to ground? What do u mean by voltage or current polarized.

2005


In control room of our one plant there is a continuously the incoming power goes to PC is vary,means in stabilizer it continuously indicate from high input to low and low input to high. what is the reason and its solution.

1594






Please help me regarding my one concern. - During earth pit testing we noticed that the Clean earth pit and dirty earth pit showing continuity (Resistance value - 5ohm) . I want to know that if both earth pit have separate location and there is not internal looping between PIT then why such continuity is showing on it . Because of this issue the field side all earthing point showing short. In PLC panel we are providing two types of earthing cable which is coming from separate earth pit (Clean and Dirty earth pit) because of earth PIT showing short our PLC is not complying spec . please help regarding this issues.

1209


There are a trformer and an induction machine. Those two have the same supply. For which device the load current will be maximum? And why?

782


Can 4pole (3 phase+neautral )RCCB proper functioning in only 3 phase load (no neautral, no Earth) ?

1796


how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?

1487


How i can calculate current of cable according to ares?

1517


How halogen & merquery lamp works.

1774


what is the use of the puls transformer in UPS & how it works???????????

1750


size of condotory fron voltage level

1845


Why we are using Isolation Power Transformer inplace of commercial power transformer? What's the difference between them?

1626


can someone explain that how the speed of the protection system affects the fault level calculation?

1565