Between Turbo alternator and Hydro alternator which one is
more difficult to cool and why?
Answer Posted / iamdon
Turbo alternators are more difficult to cool as explained
below.
Turbo alternators rotates at high speed(efficiency is high
at high speed) of 3000rpm or 1500rpm(obsolate now).
High speed of rotor limits the rotor construction as
cylindrical rotor having
LONG AXIAL LENGTH(many stages e.g, LP(Low Presuure),IP
(Intermediate Presuure) and HP(high Pressure) are employed
on common axis in case of turboalternator) and
SMALL ROTOR DIAMETER(economically suitable to house only 2
or 4 rotor poles).
Disadvantage from cooling point of view
1)There is no fanning action due to cylindrical rotor
construction.
2)There are small surface area available for direct heat
radiation.
3)Heat produced in the embadded portion of armature has to
travel a long axial distance to reach at the end for
dissipation.
Author:arbelectbit@yahoo.com
Is This Answer Correct ? | 8 Yes | 3 No |
Post New Answer View All Answers
How will A Medium voltage circuit breaker(11 kV voltage level) operate under short circuit fault condition whether It is having short circuit release like Low voltage circuit breaker or relay should be given?
What is the difference between grid and off- grid system??
Can I use star delta connected induction motor for dual supply voltage?
Explain what is electric traction? Explain few advantages of electric traction system?
how synchronous condenser is used in place of synchronous generator with out negotiating IEEE standards? Can i use 3 generators as synchronous generators and 2 generators as a synchronous condensers in an IEEE 14 bus system with out disturbing the standards?
we are having 15kw and 3kw motor both can run in same time , instead of using copper we are using ug aluminium cable , 35 sq.mm is suitable for its current carrying capacity..?
How can we connect additional batteries to three phase ups? What are parameters we have to check when connecting?
Compare jfet’s and mosfet’s.
how to select electronic timer(Star-Delta) setting for diff. rating motors
Why does the radius of armature is less than the radius of pole shoe?
When will you multiply and devide with derating factors to the actual value while sizing the cable?
who many types of fire explane with exmple
how solar power plant energy meter multiplication factor
Is it possible to use a S1 duty class motor for crane application (S4)? If not, why?
how oltc works in rectiformers of higher rating (27 mva,200v dc,120kamps) please provide me full information with diaggram.