Answer Posted / venkatesh a
For the low voltage systems NGR is not required. If it
necessary then We should consider the relay/Numerical relay
time of fault current allowable, sensing capacity.
In some industries, where the critical areas even though
fault happens they didn't allowing to trip the circuit by
relays.
They maintaining the supply as it is till the next
shutdown.
These resistance are calculated depends upon the fault
current, time delay of fault current, Relay settings.
In my site, we are using the 12.7Ohms NGR for 33/6.6Kv
6.3Mva transformer.
| Is This Answer Correct ? | 10 Yes | 2 No |
Post New Answer View All Answers
why Current is lead 90 degree and voltage is lag 90 degree in a capacitor.? why Current is lag 90 degree and voltage is lead 90 degree in an inductor.?
Why human body feel electric shock?
What are the major reasons for balancing hydro-thermal mix?
What will be the impact on motor performance if a LT motor is rewound with changed motor winding data as given below:- Original winding data: total 04 wires = 02 wires of 17 SWG + 02 wires of 16.5 SWG. Changed Winding data: total 03 wires of 15.5 SWG wire size Motor rating: 160KW, 740RPM, 415V, ID FAN application. Normal Running Current = 95% of FL Current.
how to discharge 3 phase power factor correction capacitors
Why Stabilising Resistor used in REF circuit ?
i have done diploma and btech in EE and live in Chandigarh so kindly help me how can i make my competency certificate in my area.
While testing LA mast,What are the parameter limits ?
What is oscillator circuit?
I have 1500/1A CT If i connect this CT in 6.6KV bus bar means what will be the voltage present in CT?
how will we calculate the copper wire load..
A 11KV, 1200 A breaker combination fixed in a cubicle for HT motor.Is normally for 11 KV motor fuse is using? if Yes, What range fuse is required?
I just purchased a 4 position cam switch to be used to operate a 3-speed blower motor. The motor is a 10 amp motor and has 3 wires that are used to control speed. The cam switch was rated at 660V 20 amps but when I received it, I noticed that it has AC-15 operational current rating (Ie) of 4/5 amps. If I am reading the label correctly. the 4/5 amps is related to 440v/220V (Ue). Other ratings are AC-3: 5.5A, AC2: 7.5A and AC-4: 1.5A. My questions are 1) Is it safe to use this switch with the motor I have 2) what is the difference between the 20 amp Ith ratting and the Ie operational ratings?
What are the uses of stepper motor?
The height to which the liquid in a tank to be maintained for a certain constant velocity?