Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

While connecting bulb in Series/Parallel,there is any
difference in glowing

Answer Posted / iamdon

Consider this case with two identical bulbs.The resistance
(calculated by voltage squared diveded by power rating of
bulb) of ecah bulb will be same.

Lets the resistance of each bulb is R and the supply
voltage is V.

Power absorbed in series by one bulb=(V/2)*(V/2)/R=V*V/4R
Power absorbed in parallel by one bulb=(V*V)/R=V*V/R

Clearly, the bulb in parallel glow more.Thats why household
wiring are done in parallel mode.

Author:arbelectbit@yahoo.com

Is This Answer Correct ?    3 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what will happen if the prime mover on the field excitation of the on-coming generator fails?Explain.

5553


what will happen when the dc supply is given to the capacitor?

1535


What is EMC filter in VVVF Drive ?

2735


How isolater function when installed inelectrical 440V wiring

2241


Why corona leads to production of Ozone and glow of the color VOILET?

1983


what is the basic construction diffrance between servo motor ans sqiralcage induction motor

2488


A commercial Building is designed with 14th floor levels with indoor substation of three phase transformer with rated capacity of 1000 Kva.The transformer delivered 65% of its rated capacity at 0.67 power factor lagging.Because of low power factor, the power customer was penalized and certain cost was charged accordingly based on every point percentage lower than 85%.This situation may repeatedly happen on the succeding energy bills of power customer.The power customer is desired to improve its historical power factor of 0.67 lagging and no further penalty be impose by the local power company on the next bill. Q: Identify the appropriate solution you want to offer to Client?.Justify SCIENTIFICALLY and MATHEMATICALLY the principles behind the solution.

1801


how to calculate the mesh earth network resistance in such substation, is there any recommended resistance values with references , thanks!

2340


Can we transmit digital signal to long distance ?

1958


After doubling voltage from solar cells & use step down voltage transformer can we get high current output with low voltage.

1987


I meggared my 2c*70 sq mm AL AR XLPE cable. its one end show 50 M ohm . is my cable is safe for laying. I have only one phase and neutral.

1886


What is the difference between indoor and outdoor transformer

5930


What are the advantages of autotransformer?

1221


What is the unit of attenuation?

1080


how does grading rings & spacers in transmission line works? Working Principle?

2093