Answer Posted / iamdon
If power factor became 1 then no reactive power is
required for load.
It means generating source would have to supply only real
power requirement of load.So less rated generator can be
used for feeding such load.
Also due to zero flow of reactive power,sending end voltage
is equal to receiving end(load)voltage.That is there will
no any voltage drop at the load end.
In such cases line loss is only due to real power
flow,which was otherwise(In case of non unity power factor)
due to flow of both real and reactive powers.Naturally
there will be reduced(non zero) line losses in case of
unity power factor.
| Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
how to determine motor size for a fan application?
How to determine stage of Automatic Power factor controlling Relay(Apfcr)?
what are the necessary basic electrical topics to learn for mechanical engineer to deal practical problems.
define displacement & magnitude ?
Why reactors use before incoming of ac vvfd drive?
what happen if the parallel generator phase angle shift by 1 degree in manual mode
Hi.. I am a BE GRaduate in E&E. I have 8.5 Experience in Tendering & Estimation field. I have done SAP SD course few years back. But due to some reason i failed to get job in that field and continued my own field. Now I am thinking of changing into SAP seriously. How should i go ahead???
How to discuss the phase shift of transformer considering open delta?
ult of expression 'document.FrmQF.myem
sir plz send some previous year questions of jspl.
how to calculate the earth mat design in 132 kv substation yard ????
What is servo motor? what is its purpose?
what is kondo syatem in eletrical traction
When a square wave is applied to primary of a transformer then what will be output wave form of secondary ?
Differentiate between voltage and current feedback in amplifiers?