What is the lower limit of megger value for 66/11KV power
Transformer ?
Answer Posted / dinesh lokhande
As such values mentioned above are not same for all
transformers. Because Insulation resistance consist of
summation of resistance value for composite dielectric. i.e
dielectric consist of paper, oil, metal part, wooden
barriers etc which can be considered as several
capacitances in series.
Point here is we have to find out polarisation index
PI = Megger value after 10 mins / Megger value after 1 min.
PI as a normal practice and also mentioned in some
technical papers should be more than 1.3
Considering PI we can judge measured Insulation resistance
values of insulation.
| Is This Answer Correct ? | 18 Yes | 2 No |
Post New Answer View All Answers
i have gear oil pump with single phase motor.some time its motor starts running in reverse direction rather than forward direction...whats the reason behind this issue. 1- either capacitor is week? 2- or winding is week?
For overhead protection we use which transformer?
what is conductor constant of raccun conductor
A commercial Building is designed with 14th floor levels with indoor substation of three phase transformer with rated capacity of 1000 Kva.The transformer delivered 65% of its rated capacity at 0.67 power factor lagging.Because of low power factor, the power customer was penalized and certain cost was charged accordingly based on every point percentage lower than 85%.This situation may repeatedly happen on the succeding energy bills of power customer.The power customer is desired to improve its historical power factor of 0.67 lagging and no further penalty be impose by the local power company on the next bill. Q: Identify the appropriate solution you want to offer to Client?.Justify SCIENTIFICALLY and MATHEMATICALLY the principles behind the solution.
primery try cell?
I am doing apprenticeship training at HT switch yard in NLC. How can i get electrical c license. ??? What r the rules for getting it as an apprentice? ??
why there using acb enclosure in big buildings
What is the reason of polyphase induction motor tripping suddenly on high current during running at 70% laod? Motor IR , winding resistance & inductance balance. Motor no load current is balance and ok as per mgfr. data.
What is genrally the % Impedance of a Dg set? How can we calculate Earthing conductor size for a DG set?
Dear Respected sir how to test ABB REX521 protection relay by relay tester.
where the lexical paramater will use in fron end?
What is center gravity load in substation?
Why are cables rated for 40 KA for 0.25 Sec fault current rating?
main difference between ac and dc?
What is the rating factor for copper cable ( Specific value according to the type of laying ) & the voltage drop?