What is the lower limit of megger value for 66/11KV power
Transformer ?

Answer Posted / dinesh lokhande

As such values mentioned above are not same for all
transformers. Because Insulation resistance consist of
summation of resistance value for composite dielectric. i.e
dielectric consist of paper, oil, metal part, wooden
barriers etc which can be considered as several
capacitances in series.
Point here is we have to find out polarisation index

PI = Megger value after 10 mins / Megger value after 1 min.

PI as a normal practice and also mentioned in some
technical papers should be more than 1.3

Considering PI we can judge measured Insulation resistance
values of insulation.

Is This Answer Correct ?    18 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how much excitation voltage required to generate 1mw power?

1601


When can we take Neutral as common neutral link?

1212


What is servo lock in CNC how they work and if any parameter for them in CNC machine

4794


What are the protections for safe running of electric generator?

1717


what are the things that can cause a three phase motor to crawl?

2875






what r the checklist while installing 500 kva transformer

1803


what transformer we used normally and upto which kva?

1489


Sir, plz tell me how droop setting is done in parellel operation od DG set ? please give practical example ?

1673


i applied for the ap transco please forward the freqventley asked QA

1539


before transformer oil dielectric strenght tests are taken the oil should be allowed to settle to remove option 1 air bubbles 2 gasses 3 contamination 4 water

1186


i m doing DEEE in part time,can i join regular cources in BE,,IF i join what the cources can i select like (civil,ece,IT) ,,kindly advice

1636


Is it a better option to procure screw type air compressor rather than reciprocating air compressor?If so, what is the reason?How should we select an air compressor(100 CFM)? Please mention the important parameters of air compressor.

1529


can we conduct the swineburne's test on a dc series motor? why?

1629


1.4 What is meant by CT knee point voltage and how would you determine it

1159


How to calculate MCB Breaking capacity.

973