Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I have 725KVA DG set how to Calculate the Ratio of KWH?
Whatb is the Formila

Answer Posted / satish s.nanal

The Term Ratio of KWH itself is incorrect.

KWH means Energy Consumption.It is multiplication of Watts
( Or Kilowatts) consumed over a period of time.Now
considering Power Factor of 0.8 , KW shall be = 725*0.8
= 580 KW.
Now if 580 KW are consumed for say 2 Hours then Energy
Consumption will be 580*2= 1160 KWH

Is This Answer Correct ?    30 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the purpose of high speed earth switch in gas insulated substat

2987


ht side line to earth voltage

1575


What is mean 2XWY

2492


How to reduce the static electricity producing in solvent room? By P.D.Patil BioCon

2088


I have a situation to design sub-Distribution board/Panel meant for feeding power sockets. In the incomer CAN i Take TP MCCB with Neutral Link and All the outgoing feeders with to sockets with TP MCCB and Neutral Link? P.S : My System is IT Earthing

1821


what is the reqirred voltage in HT motor to get full RPM on no load test?

2067


What is open loop and control loop systems?

1128


what is the need of starter in tube light and what type of starter is used in that?

2024


11KV AND 22KV NETWORK KW CAPACITY IN RING AND RADIAL?

1996


can indirect loading be called as phantom loading?

2192


what is the voltage rating of chiller unit sensors

2773


DESCRIBEPNEUMATIC SYSTM OF ASH HANDLING PLANT

5535


how to calculate the formula of cable size if motor kw is given

2271


i have install 750 kva distribution transformer at my site and want to do neutral earthing. what calculations should i follow to determine earthing conductor material and size?

2060


What is the actual calculation for transformer short circuit test?.

2461