I have 725KVA DG set how to Calculate the Ratio of KWH?
Whatb is the Formila

Answer Posted / satish s.nanal

The Term Ratio of KWH itself is incorrect.

KWH means Energy Consumption.It is multiplication of Watts
( Or Kilowatts) consumed over a period of time.Now
considering Power Factor of 0.8 , KW shall be = 725*0.8
= 580 KW.
Now if 580 KW are consumed for say 2 Hours then Energy
Consumption will be 580*2= 1160 KWH

Is This Answer Correct ?    30 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

in the directional overcurrent and earthfault protection,normally we are setting the angle 45 deg lead for phase fault overcurrent and -45 deg lead for earthfault fro forward direction.but both the fault are operating on the same angle region only.why?how the relay will response?

1512


EXPLAIN THE TERMS "INTEREST AND DEPRECIATION" AS APPLIED TO ECONOMICS OF POWER GENERATION.

1875


What should be the magnetic balance test values for a 3 phase delta/star connected single primary dual secondary winding transformer (90 MVA / 2 X 45 MVA TRANSFORMER)

1512


How does "OUT OF STEP" relay ,for Synchronous motor protection, work?

3977


define the non synchoronism of synchoronous machine in general g or m??

1535






How to select a cable size for particular load?

1439


How do you select the pickup value of the relay?

901


Can anyone explain me about the capacitor calculation

1799


i need of the bhel question papers along with answers and also give some website names for the downloading question (electrical and electronics engg question)please help me....

1589


HOW CAN WE DECIDE THE SUPPLY VOLTAGE FOR MOTOR ACCORDING TO ITS RATING(IF ANYONE KNOWS GIVE IT WITH EXAMPLE AND ITS CALCULATIONS)

1595


boiler is running in rankine cycle and deisel generator is....?

1652


what is inverter and converter

1512


234 MVA Generator 3 phase Short circuit current Values required? Gen set Rating-234 MVA, Gen Voltage-18kv, PF;0.8, Xdv:23.5 %, Transformer Rating-18/380KV, 680MVA,Yndd1 two winding, Step up TR, ZT:35.50 %,X/R 4.33 Gen CB Position, CB open ,Disconnected open, Generator Running Voltage 18 Kv, Bi mistakes generator side earth switch Closed during that time short circuit current level in 3 Phase required, and how to test on site 234MVA Generator Short circuit current,

1696


what is the difference b/w ground & virtual ground?

1938


What is the formula for calculating the Instantaneous Short Circuit & overcurrent for any breaker

1571