I have 725KVA DG set how to Calculate the Ratio of KWH?
Whatb is the Formila
Answer Posted / satish s.nanal
The Term Ratio of KWH itself is incorrect.
KWH means Energy Consumption.It is multiplication of Watts
( Or Kilowatts) consumed over a period of time.Now
considering Power Factor of 0.8 , KW shall be = 725*0.8
= 580 KW.
Now if 580 KW are consumed for say 2 Hours then Energy
Consumption will be 580*2= 1160 KWH
| Is This Answer Correct ? | 30 Yes | 3 No |
Post New Answer View All Answers
What is the different between digital phase converter and ordinary phase converter?
Why reactive power is needed in a power system? How is it being absorbed or delivered by alternators? For reactive power control we are changing excitation but reactive power absorbing or delivering related to stator. How these two are interlinked? i want a detailed explanation with necessary expressions and figures?
What are the types of instrument transformer?
checking procedure of capacitor based motors.used in fans etc?
For small size, high frequency coils, the most common core material is- a. )Air b. )Ferrite c.) Powdered ion d.) Steel
th how could we differentiate between armoured copper and armoured aluminium cable what is the basic application? why we prefer the armoured copper as compared to armoured aluminium.
WE know that for Inductor X=2pifL,In DC f=0,then X=0 so,V=IX=0;But In the DC excitation of rotor of AC generator,DC motor field coil which coils are inductor so why does not applying DC voltage short the rotor coil of AC generator and field coil of motor?If it would then DC source might be damaged but it is not happened. Why does the strand conductor of Electrical power transmission line make twist?
why and how current drawn by battery charger depends upon the altitude where it is located?
Convert a star connected network into a delta connected network.
how can you calculate fault level ?
if we have a industrial load of 400 kilowatts with 415 volt AC then how much total harmonic distortion (thd%) should be acceptable for steady power system.
What is Meter MF if External CT Ratio is 150/1 , PT Ratio is 132/110 Meter CT Ratio is 200/1 & Meter PT Ratio is 110/1
HOW TO DESIGN THE body EARTH cable(Copper Conductor) size for 60KVA UPS?
can we do the star delta connection of capacitor for 3- phase motor starter.
What is meant by a stray loss of a induction motor??? What is the equation to find it