Answer Posted / haancoh
Keeping it short, there are mechanical droop affecting kW
(real power) and voltage droop affecting VAR(reactive).Both
should be set the same for all generators operating in
synchronism so that the kW and VAR sharing between the
generators are more stable, especially during sudden load
change.
Is This Answer Correct ? | 12 Yes | 8 No |
Post New Answer View All Answers
How to run a three phase motor into single phase........
how can calculate resistance box for 15 kw, 6 pole, RV-230, RA-42 motor
what is The difference between national electrical code and I.S.Code (electrical) and what is the value of NEC in electrical engineering field
why in an industry; machine having rated 200 h.p stopped after power factor is maintained above 0.97 lag by control panel in view-of energy saving
how to find the capacitance value of the motor while running??
why and how current drawn by battery charger depends upon the altitude where it is located?
How does the slip regulator works as a startor
is there any lightning by passer is arranged in ship like buildings?
hi there i am highly enthusiastic about discussing electrical concepts , and hence i wud lyk to invit al do intrested to join me at gtalk and hav a dscussun of the concepts , ad me as a freind . my email id is rakesh.2k99@gmail.com
what happen if the load connected to the induction motor is taken away? the same question for synchoronous generator in synch i think that the the exitation voltage will appear on the terminal only if so plz answer me
sir i want previous entrance exam papers for written test
why the protection turbo generators is most complex?
How does zener phenomenon differ from avalanche breakdown?
Is there any relevant technique to produce power from light and heat energy of the sun simultaneosly from same rays of light?
please send me previose rrb junior engineer qustion papers