Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What is difference between earth leakage relay and
restricted earth fault relay ?

Answer Posted / prasun bhaumik

REF sense the residual or differential current in between
two sets of CTs installed at two sides of protected unit
i.e Tr or Gen. It is a high imedance differential
protection it will only operate when
1) There is a earth fault inside the object which will
produce sufficient differential current.
2) In case fault occures out side the zone any of the CT
may satuarate then it will mal operate.


But earth leakage relay is conncetd with a CT which is
commonly ring type and surronded the earthing path of the
instrument or cable with armour it operates on Over current
principle not differential principle so there is no
requirement of stabilizing resistance as in the case of REF

Is This Answer Correct ?    12 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is buffer resistance starter.?.What is the working principle and where it is used..?

2080


How to findout raw or ups power? its not indicated in socket,

2088


following are the questions asked in interviews: 1) Considering the short circuit fault, which switchgear is preferable, SFU OR MCCB? Which operates faster? whicg one is popular in Indian Market and why? 2)Define SCPD. What is type2 coodination? 3)Why the contactor rating is higher for the fuseless selection than for fuse selection? whether the ratinf of SFU or MCCB remains the same in both the cases? 4)If the HP rating is known then can you calculate the ratings of L.V Switchgear(SFU/MCCB, contactor, OLR) without using the selection chart?

2116


Load break swicth maintenance procedure.

1816


what will happen if the prime mover on the field excitation of the on-coming generator fails?Explain.

5604


please give me solution to rectify the emi(electromagnetic interference)

1972


How do we calculate the resistance per metre of single core aluminium stranded cable 19*3.25mm sheathed in pvc,at 15 deg C temperature?

2454


Explain the role of a car driver as one of a feedback mechanism.

1242


How to Calculate KA Rating of Main LT Panel

1793


Why dry type cast resin transformers tap link blast in HV side while power shut down times on load?

2394


What are the Return ( Monthly / quarterly/ Annual submitted to Electical Inspector for an establishment (Factory in Maharashtra-- Small scale category having seperate HT line of 22KV ) as per Maharashtra Electricity Act

2081


how many stairs have you climbed while you were coming

2226


in general it is observed in power stations, the tertiary winding is used in higher rating Y-Y auto transformer but not in Y-Y power transformer. is the tertiary winding is compulsory then why it is not using in power transformer 

1861


Sate maximum power transfer theorem?

1169


I want definition for ABT Meter (Availability Based tariff) ?

2038