Why in medium voltage system(3.3kv to 33kv, neutral is
earthed with either resistance, reactance or neutral
grounding resistance?
Answer Posted / avdheshlakhera
You need to limit earth fault current in medium voltage
system if rotating machines are connected to the system.By
adding NGR E/F current is limited hence during earth fault
in motors or in generators there will be less core damages.
This will reduce repairing cost of machines (Repairing of
core damages are very costly in large machines). Only thing
you need to do with resistance grounding system is to
select sensetive relays and set them correctly.
Is This Answer Correct ? | 5 Yes | 2 No |
Post New Answer View All Answers
What are the differences between single phase and three phase?
Describe the test procedure to determine the vector group
I want to merge a cable..in between two metering Cubicals which contains CT's and PT's and Energy meter..before taking merger..what are the common things required?
What is the actual calculation for transformer short circuit test?.
Single line diagram for dbb (double bus bar)system.
What is the meaning of dedicated earthing?
given data are load current & power factor cable core size? plz any one update the calculation formula
what do you mean by plant earthing system.
what is the standard duration after failure EB power
Which Class insulation is prefered for the sandwich Busducts ? Why?
What is meant by a stray loss of a induction motor??? What is the equation to find it
WITCH CARDS IN USE IN FIRE CONTROL PANEL.
how we provide neutral earth on synchronising panel as per electrical standards?
hi , i have 150 kw loud and we need 50 m cabil,i want to know wich size cabil we use. thanks
in ring main system we use the isolater b/w transfer bus and main bus if we r not use isolatar than wat will be the effect in our sys.