sir,
how to select the cable size, what is the parameters use
ang what is the formulas use for this cable size
calculations. please tell me.
Answer Posted / amarnath
To select the cable size we need to know the ampere rating
of the load and normally 1 sq.mm of Aluminium cable can
carry upto 1.2Amp and 1 sq.mm of Copper cable can carry
4.3Amp of Current but we should also consider the voltage
drop when the load is far away using the formula
VD=2KIL/cable size in CM
where VD is Voltage drop, K is the losses normally 12 for
copper and 19 for aluminium, L is the length from the
source to the load and CM is centimiles 1sq.mm in centimil
is 1943.5252.
| Is This Answer Correct ? | 25 Yes | 1 No |
Post New Answer View All Answers
what happen ehen synchronisation is done at below rated speed
how to find the multiplication factor for digital energy meter and analog energy meter
what is the prosses for getting of 33kv licence (i have completed my engineering degree & working in 33kv substation for contract basis )????
High voltage test procedure of in swgr board. why should measure millivolt drop on testing time?
How does zener phenomenon differ from avalanche breakdown?
What are the types of windings present in the ceiling fan? What winding will be effective first when we started the fan?What are the resistance and inductance ratios comparatively at the initial speed and full speed of the fan?
What is the function of the circuit breaker failure relay?
a 230v transformer with step down ratio 19:1.it has 2000turns on primary and rated 25va calculate max primary current no of secondary turns volts/turn
how copper and aluminium wires or cables are choose for current rating? please provide copper and aluminium wire selection chart for different current rating ?
Can we use 230VAC, 63A MCB for 120VAC, 63A supplied heaters load?
We normally make oil soak pits under Transformers. Oil from soak pit goes to collection pit. We provide granules/pebbles under transformers. My question is weather granules/ pebbles to be filled in soak pit or not? if yes upto what level?
You are of electrical field and you are going for software? Why
take 100kva DTR( delta/wye ), what ll happen if we connect 11kv to LT side instead of connecting to HT side? will the DTR behave as a step up transformer or something else????
In a 3 phase 4-wire system. For a 3.5 core cable if all loads are single phase and balanced, what will be neutral current? will it be sum of all phase currents? Or it will be zero? And if loads are unbalanced what will be neutral current?
What kind of maintenance is conducted for Transformer