Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Why 3 over-current and 1 earth fault relay is used on
primary side of transformer? Why 2 over-current and 1 earth
fault relay in used on secondary side of transformer?

Answer Posted / ronik

1)The reason when a double line fault occurs on secondary
side then if the transformer is of DY11 type then if 2
over-current relays are used on primary side instead of 3
O/C relays then the phase in which no relay is placed will
carry double the fault current and the in current in the
either phase will be low enough that a relay can pick
up...and meanwhile the damage will be done to the system...

2)Moreover the ground fault on the secondary side will not
have any effect on the earth fault relay on the primary side...

3)on secondary side each and every fault will be detected by
the 2 O/C and 1 earth fault relay easily...

Is This Answer Correct ?    4 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

33kv Rated output avilable in market (any where in india)

2136


technically, what is the reason behind starting the motor star the delta connection .. and what other ways to do this rather than using " star-delta transformer"

2047


what exactly commisioning work does in electrical site work... LT side?..

1993


Could the power factor on electrical system can affect the registration of the kwhr meter or the CT/PT? 

2004


How do we calculate transformer oil in liter from the rating of the transformer.

1728


I am designing new project sub station with 220 kV / 11 kV, 40 MVA capacity. This project have many recifier sets, which can generate 3rd harmonics. Now I have to select vector group of This transformer. To minimise 3rd harmonics, what care should I take in selection of Transformer Vecrtor group? If it is Y-Y with open Delta tertiary then what should be the rating & voltage of Tertiary Winding?

1915


Maintenance of transformer???

2302


how  do you choose the cable size as per amps rating & the voltage drop for the same.

1849


what is the difference b/w pvc cu conductor and cu breaded wire..?

3638


How to check the LM324 Ic

8529


what is the difference between the voltage of 5 volts capacitor and and 5volts battery?

2002


What is electrical grounding?

1261


what is the voltage regulation for unity and zero power factor?

2361


how many types are their in switchyard or substation(like D,I TYPE), what is differant between them

2172


How Self works in DG set

2113