Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Bhel supervision exam question:
If 2 generators are working in a network. And if suddenly the
field of anyone generator weakens. What will happen in the network?
1. The generator will run as motor
2. The generator will run as motor in reverse direction
3. The generator will take lighter load
4. The generator will take more load

Answer Posted / kalinath

the generator will run as motor beacuse as the field is
weakened the e.m.f devoloped is reduced across it
beacuse of this potential difference there exists a
circulating currents

Hence the resultant is absorbing power of generator

Is This Answer Correct ?    17 Yes 7 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

difference between ac series and parallel circuit

2049


number of I/O devices in siemense plc

2146


Enlists the applications of sampled data systems?

1092


Yazaki india pvt ltd interview questions qurey related

1034


How to convert 2 phase to 3 phase electricpower in induction moter?

2123


How many wall/floor flange will i use in bus duct system if we have in our design a 35th floor building.

1502


how oti and wti connections are different from each other?

2078


Whether amorphous core transformer is commercialized or not:Name of company making amorphous core transformer and what are different rating?

1805


block diagram of 2 ups system connected in parallel mode?

2082


Sir,In our company there are 3 caterpillar make(capacity:(1) 3.3KV,2.5MW(2)3.3KV,2.5MW & (3)3.3KV,1.9MW) & 1 deutz make (capacity:11KV,3.8MW)gas engines utilised,all are running in paralell. There are three transformer utilised,(1) 6.25MVA,3.3KV/22KV,Impedence voltage:6.7% used for two generator,both are 2.5MW(2)5.5MVA,3.3KV/22KV,Impedence voltage:7.2% used for one generator of 2.5MW & (3) 5.5MVA,11KV/22KV,Impedence voltage:7.8% used for one generator of 2.5MW.all generator breakers capacity of 1250Amps. Sir,I want the details of fault level calculation of generator,transformer individually & for whole system. If you require any information from me.feel free for contact me sir.pl.send the answer of my question as the earliest as possible.

2132


What is the reason of polyphase induction motor tripping suddenly on high current during running at 70% laod? Motor IR , winding resistance & inductance balance. Motor no load current is balance and ok as per mgfr. data.

2422


What is the difference between the impedance percent and impedance voltage ?

2216


For a stable system, where should the poles of a system be in a root loci plot?

1236


what is the difference b/w ground & virtual ground?

2317


how to find ratio of CT & PT in 66/11kv 12 mva supply system ? explain with calculation.

2416