HOW TO CALCULATE CT AND VT RATIO IN PRTECTION AND METERING?
Answer Posted / naveen singh
To find out Multiflying factor
1) If meter CT Ratio is not given then CT Ratio provided in
the panel has to be considered. Example if CT Ratio in the
Metering Panel is 600/5 then the M.F is 120.
2) If CT Ratio is mentioned in the Meter then Meter CT
Ratio / CT Rating Provided in the Metering panel.
Example If the CT Ratio of the Meter is 600/5 and CT
Provided in the Panel 800 /5 then Multiplying Factor will
be 600/5 /800/5. i.e., 600/800 then M.F is 3/4 (0.75)
3)In addition to this any Multiflying factor is mentioned
in the Meter then it has to be multiplied. Example if Meter
CT Ratio is 600/5 and Panel Ratio is 800/5 and M.F
mentioned in the Meter is 3 then the M.F will be (600/800)
*3. i.e., 0.75*3 =2.25
| Is This Answer Correct ? | 20 Yes | 8 No |
Post New Answer View All Answers
HOW WE CAN REDUCE THE CIRCUIT COMPLEX OF STAR-DELTA STARTER .BECAUSE NOW WE USING ONE TIMER RELAY & THREE CONTACTOR FOR MAIN,STAR & DELTA ?IF ANY IDEAS PLZ POST.THANK U
How to test the vector group of a Yd11 transformer? what are the relations to be checked between various vectors to confirm this vector group?
Classify drilling machines.
what is the difference between ups & inverter
What is meant by reactance voltage?
whati s the sludge current in ups
What do you mean by dependent and independent voltage sources?
WHAT IS START TO INDUCTION MOTER IN STAR TO DELTA OF >5HP ?
Why space heater is required for each verical bus bar chamber? if one space heater is adequate or not for anti condensation?
how we decide wire gauge for ac or dc coil and what is the basic diff. B/w these two coil?
Its possible to use 3core 2R of 240 sq.mm cable for 3phases & separely 50sq.mm 3core cable fully for Neutral for connection of PCC to MCC 3ph..4wire system?
What is the difference between Delta & Wye windings?
what is meant by impedance & transient protection?
can we do the star delta connection of capacitor for 3- phase motor starter.
Logic using 1 kV or 1,1 kV grade in house wiring Low voltage cable. Explain/suggest? some use 1kV and some prefer 1.1kV grade insulation low voltage cable why??