what r all the type of viberation measurement measuring in
turbin? what's the output of viberation sensor?
Answer Posted / banerjeenandan
The answer No 1 given by Mr.Amit is absolutely correct. You
may need some more details.
The vibration sensors used in turbine, generator etc are all
same type i.e proximity type of sensors. The sensor are
mounted at the proximity of the Turbine and generator rotor.
From the sensors one coaxial cable runs to the proximiter,
which is mounted in a seperate JB nearby. From TSI Monitors,
this Vibration probes gets +24 Volts DC. The proximeter
gives a signal 0 to -22.4 Volts DC depending upon the
vibration measured by the sensor. Generally the diatance
between the probe tip and the rotor is maintained such that
it gives -10 Volts DC when the turbine is not running.
The sensor works on eddy current principle. As the rotor
vibration increases, the eddy current generation remains
contant, but the absorption of power in terms of eddy
current increaes. This loss of power is sensed by the
proximeter and DC voltage signal is transmitter to TSI
monitor for Measurement, Controlling & Indication purpose.
| Is This Answer Correct ? | 12 Yes | 1 No |
Post New Answer View All Answers
A PLC is programmed to drive three motors A, B and C as follows : After running motor A for an hour, motor B should get ON and motor A should get OFF. And after running motor B for an hour, motor C should get ON and motor B should get OFF. And after running motor C for an hour, motor A should get ON and motor C should get OFF. (That is, a cyclic repetition with time period one hour) Now, the second condition is: If any motor gone faulty and is tripped, the consecutive motor should get ON and the faulty (tripped) motor should be eliminated from cyclic repetition. The remaining two motors should bear the cyclic repetition of one hour each. (For healthy motor take logic as high and for tripped motor take logic as low) Now, the third condition is: When motor A load(Amps) exceeds 60% of its rated load, motor B should get ON in parallel to motor A. And when both motors A & B are running in parallel, and if their load exceeds 60% of their rated load, motor C should also start in parallel to A & B. [Here the cyclic repetition is eliminated, until their loads become normal(40%)] [Take logic high(1) for load at 60% and logic low(0) for load at 40%] Now draw a flow chart or a ladder diagram to fulfill the above condition.
typical loop drawing of a simple feedback control comprising of one transmitter and one control
What is solenoid valve? Where it is used?
Can any one tell me what type of question asked for instrumentation and control interview panel??? pls mail ramashankar.goel@gmail.com
What is Alpha & Beta fctors related to Orifice Plate & its relation with flow?
How d.p. Transmitter can be applied to open tank?
where i can get training in INTOOLS and PDMS in Delhi-NCR OR north part of India. please reply with ur ans. at arunsamkaria@ymail.com
How is PH sensor works ?
Can anyone send most commonley asked Instrumentation questions and answers in cement industry please?
what is the procedure for auto tune in masoneialn 12300 series displacer type transmitter?
Explain the working of rota meter.
sir i m preparing for BARC but i am not getting any papers to prepare for this exam so please send me some sample papers to my i.d for the preparation of barc.
How to calibrate radar type level transmitter for interface level? Total liquid(liq.1 and liq.2), level both the liq individually? For. Both the liquid levels how the signal will go from transmitter to dcs? How to calibrate. Single radar 9:26:55 AM for 2 different liquids in a tank?
Sir, I am working as a Instrument Engineer in Grasim Industries. Can any body provide question answer for interview purpose
we are using centum vp as monitoring with Dell precision work station T3600 but some times PC(s) are restarted automatically . how we can solve this problem? thanks