plz explain TSM and PSM.with example suppose ct ratio is
4000/5 and tsm is .15 and plug is at 3.75 if fault current
is 8000A.so how i find relay oprating time.
Answer Posted / yvb
your PSM set for 3.75 means 3.75 times of your py.
current. if fault current is 3.75 times of 4000 i.e 3.75 x
4000 = 15000 A. your relay will operate in 0.15 sec.(
Primary Injection.)on Secondary we can say 5 x 3.75 =
18.75A flows through ur relay.
Now comming to ur case if fault current is 8000A ie. 2
times of 4000 or u can say 2 times of 5 A.
Then your relay will operate in 0.282 seconds.
| Is This Answer Correct ? | 6 Yes | 10 No |
Post New Answer View All Answers
why do we put a transformer on soak before loading it
what is parellel power factor correction?
Can I use star delta connected induction motor for dual supply voltage?
we have one oven for 12 zone we are installed ir lamp in oven we control load from thyrister and 0 to 5vdc so our zone no 8 getting bright in fraction of second so what we do.. Please answer
Explain about how is it working Earth fault'relay and wahts the resistance value of earth bed
Phase control and integral control are used for?
what is effect of 5amp fuse on 2mva pry protection of transformer
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
i am an maintenance engineer. one distribution board have 5 feeder. recently its ELR trips frequently, but it take some times after trip( 10min,20min..)but 3 feeder no load. two feeder only loaded. i checked one feeder IR value all values are above 50Mohm.but B phase to Earth is only 9Mohm.any problem about low value
sourse is 66 KV / 350 MVA, transfarmer is 1000 KVA 6.6 / 0.415 kv, iF fault is 28.75 MVA on 0.415 KV Bus then calculat the Transfarmer Impidance
Please define ohm’s law for a.c (alternating current)?
Why does the Solid state Rectifiers for 3-ph brake motors sometimes have 2 & sometimes 3 output terminals?
At the starting of dc motor and syn.motor and induction motor high current flowing through the winding. Due to this the windings burnt out. To avoid this different types of starters are used. But incase of transformer what Will be used (At starting no emf is induced in the primary winding)?
why zero sequence impedance measurement is not applicable for single phase GT
What kind of socket shall be provided for window type air conditioner with cooling capacity upto 18000 BTU/hr