What is mean CT Saturation? How to calculate?
Answer Posted / guest
CT saturation cannot be calculated, it is tested with some
instruments.CT saturation is to know at which point of
current the CT gets saturated and so the CT is no more
correct.If we are going to test A CT of ratio 100:5A than a
variable power supply through an ammeter in series and a
volt meter in parallel is connected to the secondary of the
CT.(the part the ammeter is usually connected). A graph has
to be plotted so all readings has to be recorded.First a low
voltage is fed to the CT through the variable power supply until the ammeter shows 1 amp.Say at 10 volts you got 1 amp,
it is recorded. likewise the voltage is increased till the amp meter reads 2 amps and than 3 amps.The readings are
taken till you will come to a point the ammeter reading and
the voltmeter reading is no more proportionate.
This readings are used to plot a graph with the vertical
axis for the voltage and the horizontal for the amps So you
will get a graph at 0 volt 0 amp and at 10 volts 1 amp and
so on
At one point say 10 amps you will find a small increase in
voltage will produce in a very high amp reading. This point
is known as the knee point or the saturation point.
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
why ups rating in kva? and why ups are in parellel?.why isolation transformer is used in ups?
WHERE NEUTRAL WIRE IS CONNECTED AT DOMESTIC TO TRANSMISSION LINE(SINGLE PHASE TO THREE PHASE)
What happens if the Capacitive Voltage Transformer Primary neutral is not earthed. There is a CVT between Transformer and source, and the CVT neutral of the transformer is not earthed, does it effect the transformer while charging or does it effect the transformer charging process.
If a rotary UPS is in line through grid power; What would be the impact on Power Factor if the load through rotary ups is 25% , 50% , 75% & 100%. Will the power factor reduce with less load?
What is float cum boost charging system?
Why the magneti fields are not passes from southpole to north pole
my UPS suddenly goes off and all panel light also blow off.This happens even main electric supply is not interrupted.After some time it automatically starts functioning normally.Batteries are new.
Difference between transition and diffusion capacitance
If the rated speed of a d.c. Shunt motor is1440 r.p.m, which method of speed control would you suggested to obtain a speed of 1500 r.p.m?
plese send me the oces/dgfs sylabus and previous year question pattern of electrical engg.?
What is transister define the transister ammiter ,base, colector.
1.Can we use 6.6/11KV 300sq mm xlpe 3core cable for LT use (415 Volt). 2. If we use it for LT then what is the current rating
Can double compression glands be used with regular cables?
Why does the Solid state Rectifiers for 3-ph brake motors sometimes have 2 & sometimes 3 output terminals?
how can calculate resistance box for 15 kw, 6 pole, RV-230, RA-42 motor