what is the difference between earthed and unearthed cable?
Answer Posted / n. ramesh
In unearthed cables (usually ht cables), the core
insulation will be rated for Uphase-phase as the healthy
phase conductors will be at √3 times Uphase-neutral with
respect to earth in case of a single phase to earth fault
(when laid in ground). Whereas in the case of earthed
cables, the healthy phase conductors will be at Uphase-
neutral with respect to earth even when there is single
phase to earth fault. Hence, in the case of earthed
cables, the core insulation will be rated for Uphase-
neutral.
Further, in earthed cables, a current equal to the current
through the phase conductors will flow through the shield,
which will heat up the shield. Hence, current rating of
cables meant for earthed application will be slightly lower
than the current rating of cables meant for unearthed
application for the same conductor cross sectional area.
Generally 6.6 kV and 11kV systems are earthed through a
neutral grounding resistor and the shield and armour are
also earthed, especially in industrial power distribution
applications. Such a case is similar to an unearthed
application but with earthed shield (some times called
solid bonding). In such cases, unearthed cables may be
used so that the core insulation will have enough strength
but current rating is de-rated to the value of earthed
cables.
But it is always better to mention the type of system
earthing in the cable specification when ordering the
cables so that the cable manufacturer will take care of
insulation strength and de-rating. Also it is better to
use the cables for the type of system earthing they are
meant for.
| Is This Answer Correct ? | 7 Yes | 0 No |
Post New Answer View All Answers
diff.between servo motor and ac motor
What is meant by celling voltage & current in excitor ?
what is level 2 automation?
how you configure motorvision relay (L&T make)from DCS
Explain in brief description about the operation of DG sets.
Can anybody tell abt concrete encased earthing or grounding?
What are the conditions for sustained oscillator or what is backhouse criterion?
If i am running of spindle at 2000rpm ,but How to spindle stop at the second I am resetting the machine in CNC machines
How cmd is calculated in case of energy neters
What is A check, B check, C Check & D check for a diesel Generat
What is the difference between isolators and electrical circuit breakers?
Define active and passive network?
Hi, Next week Iam appearing RRB exam for section engineer. So help me to get modal question papers for this position. Iam very thankful to you. Whether question will be fully techanical format or general form. Please give me a details regarding this exam.
Can you explain about Restricited earth fault protection scheme
what is the function of statics switch in ups and tell me parts