what is the difference between earthed and unearthed cable?

Answer Posted / n. ramesh

In unearthed cables (usually ht cables), the core
insulation will be rated for Uphase-phase as the healthy
phase conductors will be at √3 times Uphase-neutral with
respect to earth in case of a single phase to earth fault
(when laid in ground). Whereas in the case of earthed
cables, the healthy phase conductors will be at Uphase-
neutral with respect to earth even when there is single
phase to earth fault. Hence, in the case of earthed
cables, the core insulation will be rated for Uphase-
neutral.

Further, in earthed cables, a current equal to the current
through the phase conductors will flow through the shield,
which will heat up the shield. Hence, current rating of
cables meant for earthed application will be slightly lower
than the current rating of cables meant for unearthed
application for the same conductor cross sectional area.

Generally 6.6 kV and 11kV systems are earthed through a
neutral grounding resistor and the shield and armour are
also earthed, especially in industrial power distribution
applications. Such a case is similar to an unearthed
application but with earthed shield (some times called
solid bonding). In such cases, unearthed cables may be
used so that the core insulation will have enough strength
but current rating is de-rated to the value of earthed
cables.

But it is always better to mention the type of system
earthing in the cable specification when ordering the
cables so that the cable manufacturer will take care of
insulation strength and de-rating. Also it is better to
use the cables for the type of system earthing they are
meant for.

Is This Answer Correct ?    7 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the advantages og idmt relay over magnetic relay??

3720


in an electronic tri vector meter when the current and voltage sequence changes ? what is the effect of phase sequence on recording of meter

1700


best manufacturer for busbar for outdoor switchyard having double bus bar scheme, can any one share technical specification of busbar. 132kv voltage ?

1250


WHAT IS MEANT BY TV TERMINAL IN 500MVA TRANSFORMER?

1709


A commercial Building is designed with 14th floor levels with indoor substation of three phase transformer with rated capacity of 1000 Kva.The transformer delivered 65% of its rated capacity at 0.67 power factor lagging.Because of low power factor, the power customer was penalized and certain cost was charged accordingly based on every point percentage lower than 85%.This situation may repeatedly happen on the succeding energy bills of power customer.The power customer is desired to improve its historical power factor of 0.67 lagging and no further penalty be impose by the local power company on the next bill. Q: Identify the appropriate solution you want to offer to Client?.Justify SCIENTIFICALLY and MATHEMATICALLY the principles behind the solution.

1340






hello!my name is sheikh iam preparing for indian engineering servieces,please send me the old question papers..to sheikhshaazforjobs@gmail.com

1636


What is inrush current?

638


Define the term Capacitance and Inductance?

654


Can anyone explain me about the RLC based Impulse high voltage generator and how to and operation of Series resonant High voltage reactor...?

1425


how can we phase identification in a distribution line,how we recognise that which phase is coming for a house hold connection.help me............

1589


What is zero of the system?

641


On what principle electric motor works?

682


I Just want do EHS Certified Certification Distance Course From Govt approved,so can any body provide me details.

1690


The moisture in air will condense at

680


what is the current density of copper & alluminium.

1503