Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I have connected 04nos. earthings to a transformer through
04nos. earthing pits seperately. 02nos. earthings are
connected to T/F body, and 02nos. earthings are connected to
T/F neutral.T/F capacity is 2000KVA, 11KV/415V. But after
completing of 02 years successful operation ,we are
facing following problems-

1. CT/PT occured blast one time
2. HT cable box occured blast two times
3. One body earthing strip and one neutral earthing strip of
transformer are overlapping at some places. Whenever these
two strips are pressed at overlapped points, they made spark.

What is the reason of spark?

Please explain the reason & rectification of above problems

Answer Posted / ullas

the answer follows.
1. ct/pt unit blast doesn't relate with the problem. it may
due to its poor quality , or some other reasons.
2. ht cable end box blast can be occured in so many ways.
may be due to rain water entered in to the end box leading
to short circuit the phases.
or due to poor quality,etc maybe the reason.
you can do one thing.
please disconnect the earthing of ht cable armour either at
transformer side or at the double pole structure.
3. this sparking indicated that your transformer neutral is
no longer maintains zero potential.
so please first measure the voltage of neutral.
this is done by inserting a spike five meters from the
transformer and take this terminal as earth terminal of
zero potential. and between this terminal and transformer
neutral measure the voltage developed.
if it is indicating a sufficient voltage, then it is true
that your neutral is shifted from its zero position.
if there is any fuse used in the neutral circuit, change
it in to a link.
check the whole circuit for any abnormal conditions.

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

sugest any typical project ?

1865


Why is better to have a minimum ceiling voltage of 250% than 160%?

1898


What is core CT & it's function?

2119


what are the difference between AC lamp and DC lamp

2142


What does ampere turns shows?

1183


salam,hi, i need to know what the spesification of 300amp msb...

2080


Why the dc voltage drop during starting of emergency lube oil pump? The Voltage drop from 135kv to 125 kv for one min. before re-establish to 135kv?

2365


what is the use of commutator in dc motor if we supply ac ? commutator is used to convert ac to dc.and it is used to arrange the flux in unidirectional in case of dc supply. if we give ac as supply to dc motor what is the use of commutator?

2129


What is given by the definition in BIL IMP/PF = 950/395 kV. This was found in a name plate of a power transformer.

2423


can anyone please help me to find the rupturing or breaking capacity in KA of circuit breaker (MCCB,VCB,ACB etc) of HT and LT side of a distribution transformer...please help with detailed step by step answer...thank you

2044


Why PT voltages are measured with respect to ground? What do u mean by voltage or current polarized.

2418


How will change the frequency in distribution side?

1829


how we sesign the transformer give some specifion regarding design of transformers

1978


WHAT IS MEANING OF Gg & Gg IN hrc FUSE

3340


What is T’Q and X’Q and X’D ? and what is saturated as well as unsaturated ?

1830