Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I have connected 04nos. earthings to a transformer through
04nos. earthing pits seperately. 02nos. earthings are
connected to T/F body, and 02nos. earthings are connected to
T/F neutral.T/F capacity is 2000KVA, 11KV/415V. But after
completing of 02 years successful operation ,we are
facing following problems-

1. CT/PT occured blast one time
2. HT cable box occured blast two times
3. One body earthing strip and one neutral earthing strip of
transformer are overlapping at some places. Whenever these
two strips are pressed at overlapped points, they made spark.

What is the reason of spark?

Please explain the reason & rectification of above problems

Answer Posted / ullas

the answer follows.
1. ct/pt unit blast doesn't relate with the problem. it may
due to its poor quality , or some other reasons.
2. ht cable end box blast can be occured in so many ways.
may be due to rain water entered in to the end box leading
to short circuit the phases.
or due to poor quality,etc maybe the reason.
you can do one thing.
please disconnect the earthing of ht cable armour either at
transformer side or at the double pole structure.
3. this sparking indicated that your transformer neutral is
no longer maintains zero potential.
so please first measure the voltage of neutral.
this is done by inserting a spike five meters from the
transformer and take this terminal as earth terminal of
zero potential. and between this terminal and transformer
neutral measure the voltage developed.
if it is indicating a sufficient voltage, then it is true
that your neutral is shifted from its zero position.
if there is any fuse used in the neutral circuit, change
it in to a link.
check the whole circuit for any abnormal conditions.

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is sevice settings for mccb?How can be it setted?

2231


WHAT IS THE FORMULA FOR CALCULATING CURRENT RATING(DIRECT IN GROUND OR AIR) OF ARMOURED(XLPE) CABLE OF 4C,16Sqmm?

2101


Keywords: Die, Card, Coin, B/N 2 To 12

1281


what is laser diodes?

1160


Why is water motor not taking the pressure? what is the problem?

1577


What is the formula for selecting the cabels according to load? How to calculate what sq.mm cabel to be used?

1492


how to set relay setting? and example calculation...

2044


why motor range is available 22kv,30kv,37kv,45kv and so on? why motor range is not available 21kv,24,25,26,27kv and so on?

2795


What is gross error?

1141


A mass of 1200g is accelerated at 200 cm/s2by a force. The value of the force required is:(a) 2.4N(b) 2400N(c) 240 kN(d) 0.24N

2974


what is under coal gassification?

2093


SIR, GIVE ME OPGW SAG CALCULATION FORMULA I AM DAE ELECTRICAL. THANKS

6843


What are motor generator sets and explain the different ways the motor generator set can be used ?

1170


how to avoid electrical shock how capacitor store charges wat are the speed control of induction motors state faradays law flemings left hand rule what is rotary converter wat is transmission and distribution what are the sources of energy abrevation of acb,vcb,sf6,igbt what is output equation of transformer which test copper iron and iron loss are calculated what is eddy current draw a single line diagram (10 marks) draw direct online starter(10 marks)

1985


my question is how to answer the question "you are from b.tech eee background and why do you want to go for banking

1339