what will be the output of a temperature transmitter if
temperature is 120 degree celcius?
Answer Posted / lenin
Hi mydear friend,Transmitter output depends on the
transmitter calibrated range.With out knowing the
transmitter calibrated range diffucalty to tell the output
of the transmitter.If u calibrated the transmitter 0-
120deg.The transmitter ouput will be 20ma at actual temp
120 deg.If u calibrated the transmitter 0-480deg,the
transmitter ouput will be 8ma at 120deg actual temp.
| Is This Answer Correct ? | 52 Yes | 3 No |
Post New Answer View All Answers
In most instances, Inertia processes are quite uncommon. Give an example of a combined Resistance and Capacitance situation.Describe an application, which according to your understanding of the subject matter, comprises of both Resistance and Capacitance effects.
I want to apply for the universities in US,but i got the GRE score of (650+300=950)TOEFL 69/120.Is this score sufficient for applying universities please i am married i need to go to US because my husband didn't get H1 yet.please send me suggestion
Why we are using reverse action in displacer types level transmitters on some Vessels?
Where is wet leg is used?
Explain why plc require in analog input 4-20amp & 0-10 volt?
What is critcal speed. what is resonant frequency. why we want to cross crtcal speed on higher RPM (early).
䑰ҕ䔈ҕ䖠ҕ䘰ҕ䛀ҕ䝐ҕ䟐ҕ䢐ҕ䥐ҕŹ
What happen if I install my pressure transmitter below the elevation of pipe in natural gas service?
what is scale factor of proximitor & unit of the vibration.
Is there any relation between Artificial Intelligence and Instrumentation?
Please send me the sample question of Instrumentation of hpcl/iocl exam. my mail id hihi_kiholo@rediffmail.com
Can any body help to get Rsemulator 5000 free from internet if possible then give me any link or any help .
how to connect transmitter measuring sulfur process? 1-by using long impulse line or 2- by using coated short impulse line
A PLC is programmed to drive three motors A, B and C as follows : After running motor A for an hour, motor B should get ON and motor A should get OFF. And after running motor B for an hour, motor C should get ON and motor B should get OFF. And after running motor C for an hour, motor A should get ON and motor C should get OFF. (That is, a cyclic repetition with time period one hour) Now, the second condition is: If any motor gone faulty and is tripped, the consecutive motor should get ON and the faulty (tripped) motor should be eliminated from cyclic repetition. The remaining two motors should bear the cyclic repetition of one hour each. (For healthy motor take logic as high and for tripped motor take logic as low) Now, the third condition is: When motor A load(Amps) exceeds 60% of its rated load, motor B should get ON in parallel to motor A. And when both motors A & B are running in parallel, and if their load exceeds 60% of their rated load, motor C should also start in parallel to A & B. [Here the cyclic repetition is eliminated, until their loads become normal(40%)] [Take logic high(1) for load at 60% and logic low(0) for load at 40%] Now draw a flow chart or a ladder diagram to fulfill the above condition.
How to check vortex flow meter is in good condition while we do not having calibration setup?