what is the procedure for three phase motor differential
relay testing
can it do with single phase test kit?
Answer Posted / santosh kawade
Three phase motor differential relay testing can be done
with single phase test kit.
There are two type of relay testings:
1) Primary injection : In this testing entire system
(including relay, control wiring and power wiring get
checked),
2) Secondary injection : In this testing generally we check
relay only.
By using single phase test kit:
1) Primary injection :
a) Carryout shorting of all three phases of motor winding
by using short link for individual phases seperately.
b) Inject current by using current injection device (for
inzone and outzone fault)
3) Check stability of relay for outzone fault and operation
of relay for inzone fault.
2) Secondary injection :
Directly inject fault current in relay terminal and check
proper operation of relay.
Santosh Kawade
9224 69 3116
| Is This Answer Correct ? | 6 Yes | 2 No |
Post New Answer View All Answers
what is the minimum clearance between a 11KV 150KVAR capacitor cell and series reactor.can a series reactor can be mounted in the same structure of the capacitor cells structure
what is the vvvf in the dumbwaiter?? or lift. what is the actual process?/
PLZ EXPLIN ABOUT CLASS PS CLASS CT .WHY THEY R DESINED AND FOR WHAT PURPOSE?WHY OTHER CT CANT BE USED AS PS CLASS CT? EXPLAIN IN SIMPLE LAUNGAGE IF POSSIBLE PLZ GIVE CIRCIT DIAGRAM?EMAIL-RAJ_SINGH_0376@SIFY.COM
Explain about 3 phase motor fault current calculation with examples?
i m in need of current rating chart of heavy duty pvc/xlpe, cu/al cables. can somebody provide me? if yes, plz send me at ashish_patel111@yahoo.com
Define open loop control system.
How eddy current generation support the idea of train braking?
what is the purpose of high speed earth switch in gas insulated substat
what happens in the short circuited secondary transformer,if the resistance of the short circuit is increased gradually?
What is Diff btw Fire Alarm & VESDA System???
please send me RRB electrical engineer previous year questions for Sr. Section Engineer
Is it required to lay 2 runs of GI wires along with armoured cables from one power DB Machines of higher rating?
Why need 3phase machine double earthing?
What current flows in the transformer primary when its secondary is open?
How to arrange a hous hold earthing system to keep minimum earth resistance( below 7ohms).