I have connected 04nos. earthings to a transformer through
04nos. earthing pits seperately. 02nos. earthings are
connected to T/F body, and 02nos. earthings are connected to
T/F neutral.T/F capacity is 2000KVA, 11KV/415V. But after
completing of 02 years successful operation ,we are
facing following problems-
1. CT/PT occured blast one time
2. HT cable box occured blast two times
3. One body earthing strip and one neutral earthing strip of
transformer are overlapping at some places. Whenever these
two strips are pressed at overlapped points, they made spark.
What is the reason of spark?
Please explain the reason & rectification of above problems
Answer Posted / k.bhaskar
I think your neutral earth pits resistance is not
good,ensure each earth pit resistance with out grid.The
reason for sparking may be body earth is good and some
potential is there in the neutral path.
Second ensure transformer core channel to earth connection
(inside).Measure the winding resistance and unbalance load
distribution may also cause developing voltage in Neutral.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What are the special cables required for explosion proof wiring?
what is automatic voltage regulator?we can control the vlotage by using fuzzy controller in matlab?why we go for fuzzy?
How to calculate energy stored in an inductance?
how to find motors H.P. whout any rating? (only give you a motor and multimeter)
Whether 3 phase induction motorwith 100 hp capacity , Amp 160 for which sensitive earth fault relay , type CTUM 15 can be used?
Why PS class CT is always preferred for Differential protection?
when the Transmission and Distribution network where is the "feeder" lines are located? and why should be used in T&D network.....
a 100mva,400/200v transformer has leakage impdce of 10% draws a steady state line currentof---------------
what is the differance between HT motors And LT MOTORS.
PLS SEND THE RRB CHENNAI MODEL QUESTION PAPER my email id is ganesan98655@rediffmail.com
On what basis the the size of Lightning arrester for buildings are selected ?
sugest any typical project ?
why asa method ZPF method is more accurate than ASA method?
Thermal withstand capability under full short circuit conditions, in terms of number of times of occurrence of short circuit and corresponding anticipated percentage reduction in transformer life.
Control wiring of a dol starter for forward and backward