How to select a D.G set for calculated load of 110kW..?
Answer Posted / pillay
D.G if ac is rated in KVA.Usually the alternator is rated at 0.8 pf. So KW/PF=KVA. 110/0.8=137.9.KVA.
Now the D.G must have some spare power to take care of starting current and a bit of future expansion so we load the D.G at 75%.
137.9/.75=183.8KVA
Now you can buy the nearest available D.G in the market.
Maybe 175KVA or 185 KVA
Is This Answer Correct ? | 44 Yes | 8 No |
Post New Answer View All Answers
TCS IS IT COMPANY THEN WHY DO THEY NEED ELECTRICAL &ELECTRONICS ENGINEERS?
he compression ratio for a petrol engine generally lies between
What is a commutator?
how braking & making capacity of circuit breaker is calculated?
I am EEE student i want to improve my core side skills.how cn i approach it?
1. What is differential relay? How it operates? 2.How to calculate the Short Circuit Impedance in Transformer? 3.What is the alternate solution for testing of polarity by using polarity tester while its milli ammeter does not works? 4. While testing the 33KV Busbar by using Hipot kit, what should be the test voltage we have to apply? 5. What is the procedure/activities to be taken to inject the current more than 2000A by using 2000A Loading Transformer? 6. Explain how you can give the overload setting to any Motor Protection Relay for a HT motors with formula and example? 7. Why restricted earth fault protection is needed? Why can’t differential Protection is sufficient? 8. What should be the minimum and maximum ohmic value for earthing? 9. Why DC Currents are not used in transformer? 10. What is the Frequency while we step up the voltage from 220V to 11KV? Is it possible? Explain it?
How can I calculate per unit (KWH) fuel (Gas/ Diesel both) consumption 1MW unit?
What the main causes of transient interruptions on Over-Head Distribution Lines?
If increased the frequency up to 1000 then what changes shows in voltage?
What is a compensator?
what is efficient motors and how it is different from normal induction motors
Why the moulded plug comes with domestic appliances instead of assembled plug like anchor, Vinay 5/15 A.
We are preparing another project which involves Waste heat recovery from a 1 MW GE Engine. The Engine in particular gives out flue gas at 487Deg C with a flow rate of 5650 kg/hour and this can be cooled to 180 Deg C. This gives a thermal output of ~ 594 KW that is available for input to VAM via heat exchanger / boiler. Additionally 581 KW will be available from engine jacket water (temperature profile 80/ 80 Deg C and a flow rate of 50m3/hr) Our estimation is that 300 TR of cooling is possible with a suitable VAM machine(s). Please advise what is the most suitable arrangement with maximum TR and min Capital expenditure. plz reply me as early as possible
can anyone give an idea about dia calculation in cold rolling mill
what is allowed value of zero sequence impedancce of 6.6 kv nuetral earthing transformer ?what is the actual value