why generator and t/f ratings given in kva & motor rating
is in KW?
Answer Posted / pillay
We buy/fix a motor to do a specific job.Job done is measured in watts.So a machine say a pump will use up to 3 KW to run as designed than we fix a motor of 3KW or slightly bigger to run it.Now the motor is 3KW or bigger say 30 KW and the voltage is AC or DC operated is up to you.
generators are rated in KVA because we dont know at what pf will it be operated. Say you have fitted a pf correction board to maintain at 0.95pf, you dont have a guarantee it wont breakdown or take some time to adjust. What is important the generator voltage is constant and the generator dont trip or burn.So if the pf can change anytime the current also can change anytime this may make your generator to trip on overcurrent,overvoltage(leading pf)or even destroy your genset.By rating your generator by KVA with a constant designed voltage you can know the maximum current the genset can give irrespective of pf.It is a safer and sure way of protecting your generator.you can even load yor genset at 0.2 pf so long you dont exceed the rated amps or KVA.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Could u pls tell me the NPCIL electrical engineering interview questions for Executive trainee, and also guide me how to face the interview.
What is domestic transformer? Draw the connection of domestic transformer.
advantages & disadvantages of Lagging and leading power factor .
How to calculate the multiplying factor for energy meter with ct ratio given
How to decide no. of Step and Kvar for APFC Panel 40 kvar MD: 33.12 KVA Avg pf : 0.8540
what is mppt (maximum power point tracking ) and how they used in solar power generation ??? what are the main components used in mppt?????
Assuming that a dedicated neutral earthing transformer is provided for each GT generator, when the two generators are running in parallel, has consideration been given that the earth fault current from one generator stator winding be split between the two neutral earthing transformers? If so, what adverse impact will this have on the operation of the 59N and 27TN devices?
The efficiency of a 100kva transformer is 0.98 at full load as well as half load , for this transformer what is the Copper loss at full load ?
1))why we run three phase or three different circuit from a single conduit 2)) why not two circuit of different phase run in same conduit?? and why we run same three cicuit of same phae run in single conduit??
What is the general power consumption rating of CPU CRT type and Flat type, Monitor,Printer, projector, Scanner?
which type of cabel
how rectifier transformer work in electroststic precipetatore(esp?
how to select rating of HT Panel
features of hbc fuses
which mm cable should be used for 1.hp immersible pump motor for the distance of 330 metres?