Answer Posted / maharaja
1.IR VALUE SHOULD BE MORE THAN 3MEGA OHMS FOR 1KV
2.PI VALUE SHOULD BE MORE THAN 1.4
3.TAN DELTA VALUE SHOULD BE LESS THAN .07%
4.ALL TRIPING AND INTER TRIPING SHOULD BE CHECKED.
5.AFTER CHARGING WE HAVE TO CHECK THE NOISE.
6.AFTER CHARGING WE HAVE TO CHECK THE WINDING AND OIL
TEMPERATURE 4 EACH ONE HOUR INTERVAL.